background image

Eaton Electric Limited

Reddings Lane
Birmingham B11 3EZ
United Kingdom
Customer Support Centre
UK tel: +44(0) 8700 545 333
UK fax: +44(0) 8700 540 333
email: [email protected]
www.eaton.com

© 2009 Eaton Corporation
All Rights Reserved
Printed in UK
Form No. IL01900001U
March 2009

PowerChain Management is a registered 
trademark of Eaton Corporation. 

All other trademarks are property of their 
respective owners.

Remove the main outer cover from the 
EATON MEMERA CONSUMER UNIT

1.  Remove the Busbar from the transit holder.

2. Fix the back plate to the wall using the keyhole Fixings

CAUTION: DO NOT BEND & RE-STRAIGHTEN THE BUSBAR

When fi tting the Busbar into the isolator ensure that the fl exible 
live connector is fi tted beneath the busbar in the box clamp.

Fit the busbar Shield into the base and 
over the unprotected Busbar.

Fit the busbar Shield into the base and 
over the unprotected Busbar.

Remove the appropriate “Knockouts” for cable entry.

Cut the Busbar to the desired length (number of ways 
plus one tongue) the raised “Dog leg portion of the 
busbar must be fi tted to the Main Switch. Ensure the full 
portion between tongues is removed and discarded.

CABLE CAPACITY AND TORQUE SETTINGS

  

 

CABLE 

CAPACITY

ISOLATOR 2.5Nm 

50mm

2

RCD/RCBO 2.5Nm 

25mm

2

OTHERS 2.0Nm 25mm

2

Fit the Busbar/s: Ensure all terminals are fully open before installing 
the busbar, tighten all connections to the specifi ed torques.

Apply the Instruction Label & RCD resetting instructions 
(where applicable) to the inside of the door.

Affi x the required main circuit identifi cation labels 
& Sub circuit identifi cation for RCD protected 
circuits, for split loads cut as required.

Warning – Intellectual Property Rights

Eaton wishes to make it clear that it owns intellectual property rights in the product 
which it manufactures (whether or not listed in this leafl et) and that it will take legal 
action against any party found to be manufacturing, using, or selling any article which 
infringes the company’s intellectual property. All marks in this document identifi ed 
with an R symbol or a TM symbol adjacent to the mark are trademarks of Eaton.

The use to which this product is put and its place of installation is outside our control. 
Particular care should therefore be taken to follow the instructions given here and 
to ensure their continued availability in conjunction with the use of the product.

No responsibility can be accepted by us if these instructions are disregarded. Further 
copies of these instructions and information concerning the installation and proper use 
of this product can be obtained by contacting the: Technical Services Department

Reviews: