Manual operator (optional kits)
SPLIT RACK AIR CONDITIONER USER MANUAL
UM.ICUBE2.0-SRAC.SG.0822 August 2022 www.eaton.com
E-heat
Electric heating
EEV
electronic expansion valve
The parameters of the “Device Status” are shown in the following table:
Serial
number
Meaning
Display
Unit
Description
1
Unit status
Stopping / running / shutting down
—
—
2
Current state
Standby / refrigeration /
dehumidification / dehumidification
temperature compensation / anti-
condensation
—
—
3
Working state of compressor Stop / run
—
—
4
Compressor logic state
Shutdown / manual / differential
pressure / oil return / high pressure /
high exhaust temperature / low suction
/ high suction / anti-condensation /
dehumidification / forced refrigeration
/ exhaust temperature frequency limit /
normal control / start-up process
—
—
5
Outdoor electric heating
state
Stop / run
—
—
6
Compressor speed
0~120
rps
Actual speed of compressor
7
Temperature and humidity
state
Normal / high temperature deviation /
low temperature deviation
—
—
8
DC bus voltage
—
V
—
9
External machine current
—
A
—
10
Compressor phase current
—
A
—
11
Working state of electric
heating
Stop / run
—
—
12
Working state of internal fan Stop / run
—
—
13
Working state of external
fan
Stop / run
—
—
14
Speed of 1# internal fan
0~9999
RPM
1#Actual speed of internal fan
15
Speed of 2# internal fan
0~9999
RPM
2#The actual speed of the internal fan is displayed as 0
when [the number of indoor fans] = 1.
16
Indoor fan speed
0~100
%
Control speed of internal fan
17
Speed of outdoor fan
0~1000
RPM
—
18
Refrigeration demand
0~100
%
—
19
Dehumidification demand
0~100
%
—
20
Required speed of
compressor
0~120
rps
Compressor speed calculated according to demand
21
Demand opening of
electronic expansion valve
—
%
—
22
Target steps of electronic
expansion valve
—
Step
—
23
Actual steps of electronic
expansion valve
—
Step
—
24
Superheat degree
—
K
—
25
Frequency reduction state of
outdoor unit
None / bus voltage F0 / whole machine
current F1 / module temperature F5 /
whole machine current F6 / compressor
current F7
—
The outdoor unit judges itself according to the working
state of the frequency converter.
5.6.3 Protective state
On the “Main Menu” page, select the “Protection Status” option through the “ ” key, press the “
” key to
confirm access to the “Protection Status” interface, and you can view the status of each input point, as shown in
figures: 5.20 and 5.21.