Page 10
SK-90610-Y4_EN
3.4 Mechanical Mounting
p
Mount the MBP (on the UPS, on the EBM, in the rack or on the wall), see 2.1.
3.5 Installation requirements
Recommended protective devices and cable cross-sections
1. Recommended upstream protection
Refer to the UPS User Manual for circuit breaker current rating.
The circuit breaker has to be installed upstream the MBP Normal AC source.
2. Recommended cable cross-sections
3. Installation
Terminal
position
Wire
function
Terminal wire
size rating
Minimum input wire
size rating
Tightening
torque
MBP6K208
L1
Phase
0.5-10 mm
2
(20-8 AWG)
6 mm
2
(10 AWG) 105°C
10 mm
2
(8 AWG) 75°C
10 lb in
L2
Phase
Ground
MBP11K208
with
8kVA UPS
L1
Phase
4-25 mm
2
(12-4 AWG)
10 mm
2
(8 AWG) 105°C
16 mm
2
(6 AWG) 75°C
18 lb in
L2
Phase
Ground
MBP11K208
with
11kVA UPS
L1
Phase
4-25 mm
2
(12-4 AWG)
16 mm
2
(6 AWG) 90°C
25 mm
2
(4 AWG) 75°C
18 lb in
L2
Phase
Ground
Copper wire, solid or stranded.