Instructional Booklet 

IB013003EN

Effective June 2023

Instructions for installation, operation,  

and maintenance of Magnum MR2  

(integral racking) 

EATON

 www.eaton.com

Manual racking

m

 CAUTION

DO NOT USE AN ELECTRIC OR PNEUMATIC DRIVER TO RACK THE 

BREAKER.

In the case where electrical racking is not available, the breaker 

can be manually racked using a standard 3/8-inch square drive and 

ratchet (not provided) .  

Do not use an electric or pneumatic driver 

to rack the breaker.

  Raise the racking door to gain access to the 

levering screw .  (Electrical operation will be disabled when door is 

open .)  Insert the levering tool into the square socket to unlock the 

internal mechanical clutch .  You may need to forcefully “pop” the 

end of the ratchet in some cases .  You will not be able to rotate the 

levering tool until this occurs (see Figure 10) .  Once “un-locked”, the 

levering  tool can be rotated clockwise to rack into test and connect .  

It can be rotated counter-clockwise to rack to test and disconnect 

(see Figure 11) .  Do not exceed 25 ft-lb (33 .9 N·m) of torque .  The 

clutch will automatically re-engage once inward force on the tool is 

released .

Figure 10. “Un-locking” the 

clutch.

Figure 11. Manual racking.

Racking indication

While

 electrical or manual racking, there exists three discrete colored 

positions which are disconnect (green), test (yellow), and connect 

(red) (see positions A, B, and C in Figure 12) .  At these positions, the 

breaker can be closed when the racking door is fully lowered .

Figure 12. Discrete colored positions.

If racking is stopped (electrically or manually) in between disconnect 

/test or test/connect positions, there is no complete single colored 

block in these mid-positions (see Figure 13) .  At these positions, 

the breaker will not be allowed to close .  If the racking door is 

lifted, electric racking will be disabled and the door will be “held 

up” providing additional indication that breaker is not in a discrete 

position (see Figure 14) .

Figure 13. Mid-positions.

Figure 14. Door lifted and  

held up.

Once the door is “held up”, you can release the door 2 ways .  Option 

1 is to insert a racking tool and manually rack to a discrete colored 

position, until the door is allowed to drop .  Option 2 is to insert a 

small tool through the door latch release hole, and “push in” to 

release the internal door latch .  With the tool in, you can push down 

on the racking door (see Figure 15 and Figure 16) .  You can resume 

electrical racking by clearing the E4 error code .  See Diagnostics/

troubleshooting section for more information .

Figure 15. Door latch release 

hole.

Figure 16. Release door.

A

B

C

Summary of Contents for Magnum MR2

Page 1: ...ndication 5 Setting the breaker type 6 Setting the Modbus address 6 Control options 7 Option 1 7 Option 2 7 Option 3 7 Sequence of operations 7 Diagnostics troubleshooting 8 E1 Motor overcurrent 8 E2 Open motor circuit 8 E3 Motor timed out 8 E4 Magnum breaker position unknown 8 E5 Open permissive 8 E6 Communication error 8 E8 Position switch error 8 Controller diagnostic display 9 Controller mount...

Page 2: ...NNEL WITH THIS TYPE OF PRESENTATION THIS WILL HELP ASSURE THAT PERSONNEL ARE ALERT TO THESE TYPES OF MESSAGES IN ADDITION THESE MESSAGES ARE ALL UPPERCASE AND BOLDFACE All possible contingencies which may arise during installation operation or maintenance and all details and variations of this equipment are not encompassed by these instructions If further information is desired by the purchaser re...

Page 3: ...trol the system by means of a pendant Modbus master such as the Eaton Power Distribution Monitoring and Control system or separately wired I O buttons Controller can be mounted to the left side preferred or right side of the cassette If placed in other areas of the switchgear extension wires can be added with the existing terminal blocks The eight MR2 tertiary wires connect the controller to the M...

Page 4: ...e are three methods to restrict racking a Magnum circuit breaker Option 1 lockout tagout This option prevents both electrical and manual operation Push the padlock slider forward towards the breaker aligning two holes on the left side and insert a padlock see Figure 7 The MR2 will be disabled via the permissive circuit and manual racking is blocked as well The label on the levering door will show ...

Page 5: ...acking Racking indication While electrical or manual racking there exists three discrete colored positions which are disconnect green test yellow and connect red see positions A B and C in Figure 12 At these positions the breaker can be closed when the racking door is fully lowered Figure 12 Discrete colored positions If racking is stopped electrically or manually in between disconnect test or tes...

Page 6: ...available Modbus addresses are 01 to 99 for one RS485 network To set the Modbus address follow the steps below 1 Connect pendant to the controller to be programmed 2 Hold down the Intermediate button and within three seconds press and hold the Connect button until the two digit LED display begins to flash at the same time the Connect LED will begin to flash 3 Now the Test and Disconnect buttons ca...

Page 7: ...ch of the control options Pendant I O and Modbus The Enable button must be held to operate the pendant 1 Insert the breaker into the breaker cell a The breaker is now in the disconnect position b The solid green disconnect LED will be illuminated c To proceed further and rack the breaker to the connected position the breaker must be open If the breaker is closed you will see an E5 code Refer to th...

Page 8: ...communications E3 Motor timed out Condition when motor continues to run in excess of the normal required time to reach the desired position This error state condition can be caused from a malfunction of the MR2 Operator should shut off power to the MR2 controller by tripping the circuit breaker or fuse protecting the controller and manually rack out the Magnum breaker Once the Magnum breaker is re...

Page 9: ...RI RO OC AD 1 2 3 4 5 6 7 8 1 Product group 2 Gear type will always be 02 for Magnum 3 Controller firmware version 4 Pendant firmware version 5 Rack in count 6 Rack out count 7 Overcurrent count 8 Modbus address 01 to 99 Controller mounting The controller can be mounted to the left side or right side of the cassette If placed in other areas of the switchgear extension wires can be added with the e...

Page 10: ...ube is not present please contact Eaton Technical Support and order with style shown in Table 3 Magnalube can be added to the leading edges and surfaces on all primary disconnects that make contact with the cassette stabs Table 3 Greases used on Magnum PXR and PD SB Grease type Desription Magnalube G Eaton standards 53701AI Color Green Manufactured by Saunders Enterprises inc 11 51 44th Road Long ...

Page 11: ...11 Instructional Booklet IB013003EN Effective June 2023 Instructions for installation operation and maintenance of Magnum MR2 integral racking EATON www eaton com Notes ...

Page 12: ...een the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM THE COURSE OF DEALING OR USAG...

Reviews: