10
Instructional Booklet
IB013003EN
Effective June 2023
Instructions for installation, operation,
and maintenance of Magnum MR2
(integral racking)
EATON
www.eaton.com
Appendix
Circuit breakers equipped with MR2 have a thin layer of Magnalube
applied to the primary disconnects, which is shown below (See
Figure 26) . If Magnalube is not present, please contact Eaton
Technical Support and order with style # shown in Table 3 .
Magnalube can be added to the leading edges and surfaces on all
primary disconnects that make contact with the cassette stabs .
Table 3. Greases used on Magnum PXR and PD-SB
Grease type
Desription
Magnalube
®
-G
Eaton standards
#53701AI
Color
Green
Manufactured by
Saunders Enterprises inc.
11-51 44th Road, Long Island City, New York 11101
Phone (718) 729-2690
www.magnalube.com
Figure 26. Magnalube applied to the primary disconnects.