Instructional Leaflet 

IL019117EN

Effective July 2016

Installation guidelines for users of Magnum DS 

Low-Voltage Rear-Access Switchgear Assemblies 

for seismic applications 

EATON

 www.eaton.com

 

 

2.00

(50.8)

Plan view

Floor steel

Floor steel

Floor steel

34.60

(877.8)

a

 

e

a

 

e

c

 

e

c

 

e

d
e

b

 

e

Figure 1. Welding of indoor structures to imbedded floor steel—rear-access MDS, MDN, MSB, and Series NRX

®

0.19 inches (4.8 mm) weld, 4.00 inches (101.6 mm) long at two places on front and rear of each section starting 0.50 inches (12.7 mm) from each edge of structure.

0.19 inches (4.8 mm) weld, 4.00 inches (101.6 mm) long on each end of line-up in area of bus compartment.

Internal bracket on each end of line-up to be plug welded to floor steel.

Floor mounting holes, in bus compartment, to be plug welded to floor steel.

For nuclear installations, weld per AWS D1.1, alternatively, welding procedures and personnel qualifications may be performed IAW ASME BPVC Section IX and  

the inspections be performed IAW AWS D1.1, and/or D1.3 and/or D9.1.