![Eaton Magnum DS Series Instructional Leaflet Download Page 7](http://html1.mh-extra.com/html/eaton/magnum-ds-series/magnum-ds-series_instructional-leaflet_4123205007.webp)
7
Instructional Leaflet
IL019116EN
Effective July 2016
Installation guidelines for users of Magnum DS
Low-Voltage Front-Access Switchgear Assemblies
for seismic applications
EATON
www.eaton.com
Detail A
Seismic wallmount brace
(shipped installed on gear)
A
1/2-inch tie-down
hardware
IMPORTANT: When using the
wallmount brace, plenum must
be installed on switchgear after
the switchgear is secured to wall.
a
c
Figure 6. Magnum switchgear front-access rear frame seismic wall brace arc-resistant specific information
a
Secure enclosure to pad and/or wall with Grade 5 hardware.
b
Front compartment must be secured to pad for both rear frame wallmount and rear frame floormount applications (see Detail B on
Figure 4
).
c
A distance of 2.00 inches (50.8 mm), between the wall and the rear of the switchgear, is required to properly secure Front-Access Switchgear when using the rear wallmount brace.