O & M Manual IM05805023K
Jockey Pump Controllers
www.chfire.com
Page 10
EATON CORPORATION
4.1.3 DECIMAL POINT: (1000)
While holding the PGM button, press the UP Arrow button.
The display will show “dp”
Release the PGM button
The display will show “1000”
Do not change the setting.
4.1.4 OFFSET Minimum Transducer Pressure: (0 psi)
While holding the PGM button, press the UP Arrow button.
The display will show “OF”
Release the PGM button
The display will show “+0000” – note: the “+” flashes
Do not change the setting.
4.1.5 FULL SCALE VALUE Maximum Transducer Pressure: (500 psi)
While holding the PGM button, press the UP Arrow button.
The display will show “FS”
Release the UP Arrow and PGM buttons
The display will show “+0500” – note: the “+” flashes
Do not change the setting.
4.1.6 RELAY 1 – Hi ALARM SETPOINT: (+9999)
While holding the PGM button, press the UP Arrow button.
The display will show “1Hi”
Release the UP Arrow and PGM buttons
The display will show “+9999”
Do not change the setting.
4.1.7 RELAY 1 – Lo ALARM SETPOINT: (+
0000
) Pressure Start Point
While holding the PGM button, press the UP Arrow button.
The display will show “1Lo”
Release the UP Arrow and PGM buttons
The display will show “+0
0
00”
Push the RIGHT Arrow button to move the value setting position
Set the desired START Point value using the UP and Down Arrow buttons
(eg: For 100psi, the display will show “+0100”)
4.1.8 RELAY 2 – Hi ALARM SETPOINT
While holding the PGM button, press the UP Arrow button.
The display will show “2Hi”
Release the UP Arrow and PGM buttons
The display will show “+9999”
Do not change the setting.
PGM +
dp
1000
+0000
+0500
+0
0
00
+9999
EATON XTJP / XTJY
PGM +
PGM +
PGM +
PGM +
OF
FS
1Lo
1Hi
Effective:
June
2012
PGM +
2Hi
+9999