Jockey Pump Controllers
START PRESSURE
The pressure is set in PSI format.
(To set in BAR format, refer to the JOCKEY Touch™ Operation Manual.)
Using the number buttons, enter the start pressure.
Pressing the
Arrow
button will delete the pressure values one character at a time.
Once the pressure is programmed, press the
Next
button.
Pressing the
Cancel
button will return the display to the Panel Setup 1/2 screen.
All Quick Setup values must be re-entered.
STOP PRESSURE
The pressure is set in PSI format.
(To set in BAR format, refer to the JOCKEY Touch™ Operation Manual.)
Using the number buttons, enter the stop pressure.
Pressing the
Arrow
button will delete the pressure values one character at a time.
Once the pressure is programmed, press the
Next
button.
Pressing the
Cancel
button will return the display to the Panel Setup 1/2 screen.
All Quick Setup values must be re-entered.
MINIMUM RUN TIMER
The minimum run time can be set up to 999 seconds.
The timer can be disabled by pressing the button.
To re-enable the timer, press the
Arrow
button.
(The timer values are erased and must be re-entered).
Using the number buttons, enter the minimum run time.
Pressing the
Arrow
button will delete the timer values one character at a time.
Once the minimum run time is programmed, press the
Next
button.
Pressing the
Cancel
button will return the display to the Panel Setup 1/2 screen.
All Quick Setup values must be re-entered.
SETUP COMPLETE
Once all the functions have been set, press the OK button.
The display will return to the Main Display Screen.
Pressing the
Cancel
button will return the display to the Panel Setup 1/2 screen.
All Quick Setup values must be re-entered.
SET DATE
The date is set in MM/DD/YY format.
Using the number buttons, enter the current date.
Pressing the
Arrow
button will delete values one character at a time.
Once the date is programmed, press the
Next
button.
This will advance the screen to the Quick Setup screen for setting the Start Pressure.
Pressing the
Cancel
button will return the display to the Panel Setup 1/2 screen.
All Quick Setup values must be re-entered.