Instruction Manual 

IM01005014E

Effective December 2018

Eaton  Innovative Technology 

XT50/100 surge protective device 

  

EATON

 www.eaton.com

Ground

Circuit

interrupt

device

SPD

Direct current (DC)

48 V, 125 V

Power

supply

(+/–)

(+/–)

Figure 12. Before installation as SPD

Before installation as SPD

Step A

Verify system voltage does not exceed maximum suggested 

operating voltage listed in table .

• 

All voltage measurements should be completed with a  

DC voltmeter

• 

Do not install suppressor if measured voltage exceeds 

maximum suggested operating limits

Table 2.  Maximum suggested operating voltages and wire colors

Model  

number

Line-to-line

Line-to-ground

(+/–)  

Wire color

Ground  

wire color

XT50-048DC

130

65 

Black

Green

XT50-125DC

288

144

Black

Green

Step B

Choose suppressor installation location so leads are kept as 

short and straight as possible . 

Suppressor must be connected 

to electrical system via one of the following circuit interrupt 

devices:

• 

1–two-pole/single-throw 30 A circuit breaker 

ote:

N

Pre-existing breakers of rated load size may be utilized if provisions  

for multi-conductor connections are made according to NEC 110 .14A .

• 

2–single-pole/single-throw 30 A circuit breakers

• 

2–30 A Class RK5 fuse(s) (such as Bussmann FRN-R-30 for  

less than 125 Vdc)

ote:

N

For isolated ground, suppressor GROUND wire is bonded to shell 

internally . If system utilizes isolated ground, then suppressor shell must be 

isolated from ground via insulated conduit fitting and ground wire must be 

connected to isolated ground bus .

Before installation as secondary surge arrestor

Step A

Follow Step A as above .

Step B

No circuit interrupt device is required .

Installation instructions as SPD

Step 1

Remove power from electrical system before installing suppressor .

Step 2

Mechanically mount suppressor:

• 

Suppressor to be installed through panel knockout and via 

suppressor optional (these are not on this unit) mounting feet . 

Place suppressor against mounting surface and mark feet 

positions if applicable . Complete conduit connection installation . 

Screw box to surface with appropriate screws

• 

Ensure weatherproof conduit and fittings are used to maintain 

NEMA 4 rating

• 

Suppressor to be mounted for shortest and straightest possible 

wire installation from suppressor to system bus . Excessive 

wire length and sharp bends degrade suppressor performance; 

therefore, avoid excessive wire length and sharp bends when at 

all possible

• 

If installing on a system other than electrical panel, mount in close 

proximity to system being protected using necessary means for 

mounting

ote:

N

A circuit interrupt device is still required when installing suppressor on 

a system other than electrical panel .

• 

Suppressor contains no position-oriented components and can be 

mounted upside down or sideways . (Cover may be rotated only  

180 degrees to improve label readability . Take care to support cover 

to prevent damage to indicator light circuit board and wiring .)

 WARNING

COVER WILL NOT SEAL WHEN ROTATED ONLY 90 DEGREES. THIS 

INVALIDATES NEMA 4 RATING AND MAY CREATE SAFETY HAZARD.

Summary of Contents for Innovative Technology XT50

Page 1: ...ber 2018 Supersedes January 2014 Contents Description Page Introduction 2 Installation 2 Specifications 7 Operation 7 Warranty 8 Disclaimer of warranties and limitation of liability 8 Eaton Innovative...

Page 2: ...ICAL SYSTEM FAILURE TO DISCONNECT THE SPD DURING A HIGHPOT TEST WILL RESULT IN DAMAGE TO THE SPD AFTER INSTALLATION THIS DEVICE IS NOT REPAIRABLE AND CONTAINS NO SERVICEABLE PARTS IF THE UNIT SHOULD M...

Page 3: ...ths Keep conduit length as short and straight as possible XT50 SURGE PROTECTIVE DEVICE Innovative Technology SPD Products Innovative Technology SPD Products SURGE PROTECTIVE DEVICE SEE WARNING LABEL D...

Page 4: ...for AC units IMPORTANT BE SURE TO FOLLOW ALL NATIONAL STATE AND LOCAL ELECTRICAL CODES WHEN MAKING WIRING CONNECTIONS WHEN CONNECTING THE WIRES FROM THE SPD TO THE ELECTRICAL SYSTEM CUT THE WIRES AS...

Page 5: ...it phase 1S101 SPD Phase A Ground Phase B high leg Phase C Phase C BLK Phase B BLK Phase A BLK Ground GRN Neutral WHT Neutral Figure 8 High leg 3D101 SPD Phase A Neutral Ground Phase B Phase C Phase C...

Page 6: ...via insulated conduit fitting and ground wire must be connected to isolated ground bus Before installation as secondary surge arrestor Step A Follow Step A as above Step B No circuit interrupt device...

Page 7: ...th Edition Type 1 and Type 2 SPD CSAT Type 1 and Type 2 SPD UL 96A Compliant Yes NFPA 780 Compliant Yes ROHS Compliant Yes Wire Length and AWG Factory prewired with 16 inches of 10 AWG wire a DC model...

Page 8: ...n finds the return to be a manufacturer s defect the product will be returned prepaid Copyright by Eaton Moon Township PA USA All rights reserved No part of this document may be reproduced in any way...

Reviews: