background image

Page 5

                                                                                                                          IL01222025E 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Effective 11/2007

 

 

LOCK-OFF  

Move slide knob to AUTO position. 

Pull out the Lock-Off lever when 

breaker is in OFF position, insert

 

one or two padlock shackles up 

to .25 inch (6mm) in diameter. 

 

CAUTION 

The motor operator cannot be 

locked off while it is in the ON 

position. 

 

 

 

 

 

 

 

 

 

 

 

Lock-Off Lever 

Electrical Operation 

  Make sure the slide knob is located in the AUTO position. 

  Operating the OFF remote control switch will cause the breaker to go to its OFF position. 

  Operating the ON remote control switch will cause the breaker to go to its ON position. 

  Press the manual PUSH-TO-TRIP button on the breaker to verify that the breaker moves to the trip 

position. Operating the OFF remote control switch again will reset the breaker.   

  Status window indicates Green / OFF, Red / ON and White / Tripped. 

  Always remove the operating key and move the slide knob to the AUTO position before operating 

electrically.

Summary of Contents for IL01222025E

Page 1: ...EQUIPMENT WHILE IT IS ENERGIZED DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING 1 CONTENTS Motor operator 1x Mounting Screws 103 5 mm 4x Mounting Screws 103 5mm Groove 4x Mounting Screws 10 mm 4x Springwashers φ4mm 8x Washers φ4mm 8x Nut M4 4x WARNING ...

Page 2: ...ition first Line up breaker handle and molded trigger of motor operator and position motor operator on the breaker 4 Molded Trigger Mounting Screws 10 mm Lock washers Flat washers Breaker Handle Mount motor operator to breaker using mounting screws lock washers and flat washers supplied Torque to 0 44 to 0 6 N m or 4 to 5 in lb Mounting Screws 10 mm Spring washers Flat Washers Mounting Screws 103 ...

Page 3: ...ed Leave breaker in the ON position Press the manual PUSH TO TRIP button on the breaker to verify that the breaker moves to the trip position Turn the operating key clockwise approximately 180 again This should reset the breaker Status window indicates Green OFF Red ON and White Tripped Always remove the operating key and move the slide knob to the AUTO position before operating electrically Slide...

Page 4: ...rush Current 208 240 VAC 110 127 VAC 50 60 Hz 220 250 VDC 110 125 VDC DC 1 A 24 VDC DC 3 A 48 VDC DC 2 A 1 A minimum 150 VA power source is recommended 2 Maximum rate of operation 6 operations per minute 208 240VAC 220 250VDC Application 24VDC Application 110 127VAC 110 125VDC Application 24VDC 48VDC Application ...

Page 5: ... is located in the AUTO position Operating the OFF remote control switch will cause the breaker to go to its OFF position Operating the ON remote control switch will cause the breaker to go to its ON position Press the manual PUSH TO TRIP button on the breaker to verify that the breaker moves to the trip position Operating the OFF remote control switch again will reset the breaker Status window in...

Page 6: ...Page 6 IL01222025E Pittsburgh PA U S A Effective 11 2007 IL01222025E 9 Motor Operator Outline Dimensions ...

Reviews: