DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
C
1 of 2
032406
164201536-8
INTERFACE WIRING INSTALLATION
NOTES AND TERMINAL CONNECTIONS
BATTERY
CABINET
#1
6
7
8
TB1
BATTERY AUX +
5
BATTERY AUX -
BATTERY UVR +
BATTERY UVR -
UPS
UV
BATTERY
CABINET
#2
UV
BATTERY
CABINET
#4
UV
BATTERY
CABINET
#3
UV
TB1
TB1
TB1
6
7
8
TB1
BATTERY AUX +
5
BATTERY AUX -
BATTERY UVR +
BATTERY UVR -
UPS
BATTERY
CABINET
UV
TB1
TB1
MULTIPLE BATTERY CABINETS
SINGLE BATTERY CABINET
Installation Information
A-17
EATON
Powerware
®
9390 Integrated Battery Cabinet (Models IBC-S and IBC-L) Installation Manual
S
164201536 Rev D
www.eaton.com/powerquality
1.
Use Class 1 wiring methods (as defined by the NEC) for control wiring. Install the control
wiring in separate conduit from the power wiring. The wire should be rated at 48V, 1A
minimum.
2.
Battery Aux and UVR wiring should be a minimum of 18 AWG.
3.
UV trip requires 48V to activate.
4.
Torque screw terminals to 20 lb in.
5.
Auxiliary Contacts are rated as follows:
240 VAC @ 15A
125 VDC @ 0.3A
250 VDC @ 0.15A