Installing Battery Cabinets
3-10
EATON
Powerware
®
9390 Integrated Battery Cabinet (Models IBC-S and IBC-L) Installation Manual
S
164201536 Rev D
www.eaton.com/powerquality
3.3.3
Standalone IBC-S Installation
Use this procedure to install a standalone battery cabinet (see Figure 3‐7).
UPS Cabinet
Battery Cabinet
Figure 3‐7. UPS with Standalone IBC-S
1.
Verify that the UPS is properly installed and secured. Refer to the appropriate
Powerware 9390 UPS Installation and Operation Manual, as referenced in
paragraph 1.6, for installation instructions.
2.
Roll the battery cabinet to the area where the battery cabinet is to be installed.
3.
Secure the battery cabinet in position by lowering the leveling feet until cabinet is
not resting on the casters and the cabinet is level.
4.
Remove the field kit. The field kit is attached with cable ties to the frame inside
the door. Retain the field kit for later use.
5.
If installing more than one battery cabinet, proceed to Step 6; otherwise, proceed
to paragraph 3.3.4.
NOTE
When a UPS system is ordered together with battery cabinets for standalone
installation, the first battery cabinet is supplied with two cosmetic covers. Additional
battery cabinets are supplied without cosmetic covers. Cosmetic covers must be ordered