24
Eaton 93PM Integrated Battery Cabinet (IBC-L, IBC-LH [432V], and IBC-LH [480V]) Installation Manual 164000228—Rev 08
Table 5. Line-Up-and-Match External Power Wiring Recommendations – Eaton 93PM IBC-L and 93PM IBC-LH
Battery Cabinet to UPS
Model
UPS Model
Number of
Cabinets
Terminal
Recommended Conductor Size
(AWG or kcmil)
Number per Pole
93PM IBC-L
50 kW
100 kW
150 kW
200 kW
1, 2, 3, or 4
Battery (+)
Factory Supplied
1
Battery (–)
Factory Supplied
1
Ground
#4
one per
cabinet
400 kW
1, 2, 3, 4, 5, 6, 7,
or 8
93PM IBC-
LH
50 kW
100 kW
150 kW
200 kW
1 or 2
Battery (+)
Factory Supplied
2
Battery (–)
Factory Supplied
2
Ground
#1
one per
cabinet
400 kW
1, 2, 3, or 4
NOTE
Standalone IBC-L installations with three or more IBCs or IBC-LH installations with two
or more IBCs require a customer supplied external tie point and circuit breaker or
disconnect between the IBCs and the UPS.
Summary of Contents for IBC-L