Conversion kit LED
6
DEFINITION OF ORDER CODES:
Indicating LED Cable:
__ : having indicating LED only
TB: having indicating LED and NC Test Button
Remote connection:
_: Telecommand
CGL: Connection for CGL+ bus
D:
Connection for DALI bus
Battery cell number / size:
4AA: NiCd AA/0.8Ah
xCS: NiCd CS/1.7Ah (3 or 4 or 5)
xD: NiCd VTD/4Ah (3 or 4)
2L: LiFePo4/3.2Ah
Converter output voltage range:
L: Low voltage range 3..33Vdc (SELV)
M: Medium voltage range 20..55Vdc (SELV)
H: High voltage range 40-180Vdc
TECHNICAL SPECIFICATIONS:
System Mode
Non-Maintained
Mains input voltage
230 V AC ±5% (218,5 - 241,5 V AC)
Mains frequency
50/60Hz
Mains Consumption
20mA AC max @ AA & L cell battery
30mA AC max @ CS & D cell battery
Power factor
0,47
Recharge period
24 hours / 16 hours on 2h variants
*on LiFePo variants charging temperature
range is between 0
o
C..50
o
C
(battery protection)
Charging monitor
Green LED with cable 1m
Bi-color LED (Green/Yellow)
with cable 1m - CGL+
Bi-color LED (Green/Red) with
cable 1m - DALI
Test facility
by Normally Closed Push button
by Normally Open Push button*
by Telecommand signal*
*not applicable on CGL+/DALI variants
Duration
1 or 3h, selectable by jumper,
2h/3h only variants available
Ambient temperature
range (t
a
)
5..40°C / 5..50°C (LiFePo)
Case temperature max (t
c
) converter: 60°C battery: 50°C
IP rating
20
Overheating protection
110°C
Short circuit protection
Non-inherently short circuit proof
Weight
125gr
STANDARDS:
Complies with:
EN 61347-1, EN 61347-2-7,
EN 55015, EN 61547, EN 61000-3-2
According to:
EN 60598-2-22,
EN 61347-2-13, RoHS
OVERVIEW
Conversion kits allow your existing fitting to provide
up to 3 hours of emergency lighting in the event
of a power failure. They are easily installed within
the existing fitting or in specially designed external
mounting enclosures. The kits are available for LED
lamps operating on the range of 3 to 180Vdc.
PREPARATION
Before using the converter, plan you conversion
carefully, read this leaflet and follow the instructions
given in order to comply with current legislation. It is
Installation Instructions