HMi Series Instruction Leaflet
MODEL
HMI04BU
HMI04CU
HMI06BE
HMI06GE
Power
Consumption
(Note 5)
2.64W
3.36W
7.2W
7.2W
Voltage Endurance
AC500V for 1 minute
(between charging (DC24 terminal) and FG terminals)
Operation Temp.
32°F ~ 122°F (0°C ~ 50°C)
Storage Temp.
-4°F ~ 140°F (-20°C ~ +60°C)
Ambient Humidity
10% ~ 90% RH [0 ~ 40°C], 10% ~ 55% RH [41 ~ 50°C]
Pollution Degree 2
Shock
30G @ 11ms
Vibration Resistance
IEC 61131-2 Compliant
5Hz f
≦
<
9Hz = Continuous: 1.75mm / Occasional: 3.5mm
9Hz f 150Hz = Continuous: 0.5g / Occasional: 1.0g
≦ ≦
X, Y, Z directions for 10 times
Backup Battery
3V lithium battery CR2032 x 1 / Battery life: 5 years
Backup Battery Life
It depends on the temperature used and the conditions of usage, about
3 years or more at 25oC.
Buzzer
Multi-Tone Frequency (2K ~ 4K Hz) / 85dB
Dimensions
(W) x (H) x (D) in Inches
(mm)
5.54 x 4.13 x 1.76
(140.8 x 104.8 x 44.8)
7.25 x 5.67 x 1.85
(184.1 x 144.1 x 47)
Panel Cutout
(W) x (H) in Inches (mm)
4.68 x 3.65
(118.8 x 92.8)
6.79 x 5.21
(172.4 x 132.4)
Weight
in Lbs. (kg)
.69 (.315)
.62 (.310)
1.69 (.768)
NIT Rating
100 cd/m
2
300 cd/m
2
130 cd/m
2
NOTE
1)
The half-life of backlight is defined as original luminance being reduced by 50% when the maximum
driving current is supplied to
HM
i
. The life of LED backlight shown is an estimated value under 25
o
C
normal temperature and humidity conditions.
2)
Program memory is used for recipes.
3)
USB Host port can provide up to 5V/ 500mA of power.
4)
Please use isolated power supply (not applicable for HMI08CE and HMI10CE).
5)
The value of the power consumption indicates the electrical power consumed by
HM
i
only without
connecting to any peripheral devices. In order to ensure the normal operation, it is recommended to
use a power supply which the capacity is 1.5 ~2 times the value of the power consumption.
6)
For further details, please visit the Eaton website
EATON CORPORATION
www.eaton.com 16