Explosion-protected safety switch 10A,  
GHG 261

Technical data

1.1   Safety switch GHG 261 ..

ATEX type examination certificate:

PTB00ATEX1074

Marking acc. to 2014/34/EU

D

 II 2 G Ex de IIC T6

and standard: EN 60079-0

D

 II 2 D Ex tD A21 IP66 T 80°C

IECEx type examination certificate:

IECEx BKI07.0014

Category of application: IEC 60079-0

Ex de IIC T6
Ex tD A21 IP66 T 80°C

Rated voltage:

500 V, 50/60 Hz

Rated current:

10 A

Perm. short circuit back-up fuse:

up to UN 400 V  up to UN 500 V
20 A gL 

16A gL

Switching capacity AC 3:

10 A 

10A

Perm. ambient temperature: 
(

Deviating temperatures possible with special versions.)

-55° C to +52° C (standard version)

Perm. storage temperature in original packing:

-55° C to +52° C

Degree of protection. to EN/IEC 60529:

IP 66 (standard version)

Insulation class acc. to EN/IEC 61140:

II - plastic terminal boxes fulfil this requirement
I  - with metal flange

Cabel entry: 
suitable cables and test torques of the  
pressure screw

 
M20

 
M25

 
M32

Seal 1+2+3 
(Ø mm / Nm)

1

2

3

min. 
max. 

(1)(2)

  5.5 / 1.5 
  7.0 / 1.0

  8.0 / 1.5 
10.0 / 2.0

Seal 1+2 
(Ø  mm / Nm)    

1

2

3

min. 
max. 

(1)(2)

  7.0 / 1.5 
  9.0 / 1.4

10.0 / 2.3 
13.0 / 2.6

14.0 / 3.0 
17.0 / 4.0

Seal 1 
(Ø  mm / Nm)    

1

2

3

min. 
max. 

(2)

  9.5 / 1.0 
13.0 / 1.7

13.5 / 1.3  
17.5 / 2.3

17.5 / 1.5 
21.0 / 1.3

Test torque for screw in thread cable entry:

2.7

3.0

5.0

Terminals:  

 

2 x 1.5 - 2.5 mm²

Cover screws:

2.50 Nm

Terminals main contacts:

2.00 Nm

Terminals auxiliary contact:

2.00 Nm

(1)

 

The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can 

vary by using cables with different manufacturing tolerances and material properties. Please use the combina-

tion of sealing 1 + 2 + 3 for the intermediate region.

(2) 

When selecting the seal rubber, ensure that the cap nut can be tightened when carrying out any future 

maintenance work on the cable entry.

1.2   Auxiliary contact:

Rated voltage:

500 V, 50/60 Hz

Rated current:

10 A

Perm. short circuit back-up fuse:

16 A gL up to 500 V

Switching capacity:

AC 15  

230V / 6.0 A 

400 V / 6.0 A

DC 13 

  24V / 6.0 A 

230 V / 0.4 A

Design with gold-tipped contact:

max. 400 mA

Terminals:

2 x 0.5 - 2.5 mm²

Safety instructions

a

The operations must be carried 
out by electrical suitably trained in 
hazardous area with knowledge of 

increased safety explosion protection  
IEC/EN 60079-14.

The safety switches GHG 261 are not suited 
for use in Zone 0 and Zone 20.

The temperature class and type of protec-
tion stated on the apparatus shall be 
observed. 

The requirements of the IEC/EN 60079-31  
regarding excessive dust deposits and 
temperature to be considered from the user.

To ensure adherence to the temperature 
class stated on the type label of the 
apparatus, the permissible ambient 
temperature, the rated terminal cross 
section and the self heating of the apparatus 
that is mainly due to the power dissipation 
shall be taken into account (test criterion for 
the self heating is an overload of 10%).

They shall be used for their intended 
purpose and shall be in a perfect and clean 
state.

Prior to being put into  operation, the 
control units shall be checked in accordance 
with the instructions as per section 6.

Warning: 
The covers of the safety switches can only 
be removed when the switch is in the “ON” 
position.

The national safety rules and regulations for 
the prevention of accidents, as well as the 
safety instructions included in these 
operating instructions, that, like this text, 
are set in italics, shall be observed!

Conformity with standards

They have been designed, manufactured and 
tested according to the state of the art and to 
DIN EN ISO 9001:2015 and  
EN ISO/IEC 80079-34:2011.

The apparatus are conform to the standards 
specified in the EC-Declaration of conformity, 
enclosed separately.

Dimensions in mm

 GHG 261 ..

X = Fixing dimensions