Circuit Breaker UL 489
FAZ-...-NA
Spacings for multiple pole installations
where breakers are mounted adjacent
to each other and are connected to
different polarity circuits must be
maintained as following:
Through Air
19.1 mm
Over Surface
31.8 mm
In conjunction with an upstream device fuse up to 4
x I
n
FAZ-XIS..., FAZ-(PN-...), FAZ-...-NA
+
Supplementary Protector
Technical Data
USA/Canada
UL 1077
CSA 22.2 No. 235 – M89
FAZR
FAZS
6 A to 40 A
1 A to 16 A
1 phase:
5 kA – 277 V ~ 60 Hz
3 phase:
5 kA – 277/480 V ~ 60 Hz
Tripping Current:
155 % of rated current
at 30 °C
Cu 75 °C, min. AWG 18,
max. AWG 4; Nm 2.4
6 A to 63 A
FAZB
FAZC; (FAZ-...-DC)
FAZD
0.5 A to 63 A
0.5 A to 40 A
(max. 100A)
MA-FAZ/AZ.cdr / 03.2020m / IL019148ZU / 150501140