Installation & User Manual 

Kit Navy Low Frequency Filter Module 

 

 

EX RT 7 
EX RT 11 

 

  

34008139XT/AC

 

 

 

8.1 EX RT 7 ET EX RT 11 

The cable to connect the filter module to the UPS is not provided.   

Achieve the connections on the different terminals (input and output) of the 
filter module, comply with the cable capacity as recommended here under.   
Open the low frequency filter module connection box, 
Connect on AC input terminals the cable to supply the filter module 

(recommended cable capability 10 mm²),   
Lock the presses tow,  
Close the low frequency filter module connection box,   
Connect the other extremity of the cable on the UPS input terminals, see section in the UPS 

installation & user manual,   
Connect the load on UPS output.   
 
 

9. UPSTREAM RECOMMENDED PROTECTION 

Nominal power of the UPS 

Recommended circuit breaker 

7 kVA 

D curve – 40 A 

11 kVA 

D curve – 63 A 

 
 

10. COMMISSIONING 

On the filter side, take care to close the input switch. 
Then follow the UPS user manual, commissioning chapter. 