34008097EN/AE
- Page 13
2. Installation
2.6 Connections with a Fle PDU
(Power Distribution Unit)
module
(optional)
2.7 Connections with a HotSwap MBP module
(optional)
The
HotSwap MBP
module makes it possible to service or even replace the UPS without affecting the connected
loads (
HotSwap
function).
RT model
1 - Connect the UPS socket
(9)
to the AC-
power source using the power cable from
the equipments to be protected.
2 - Connect the input socket on the
FlexPDU
module
(48)
to the UPS outlet
(7)
or
(8)
using the cable
(40)
IEC 10A/16A
supplied.
The cable and the connectors are marked
in red.
3 - Connect the equipment to the outlets
(45), (46)
and
(47)
on the
FlexPDU
module.
These outlets differ, depending on the
version of the
FlexPDU
module.
4 - Fit the connection securing system that
prevents the plugs from being pulled out
accidentally.
RT model
1 - Connect the input socket
(56)
on the
HotSwap MBP
module to the AC-power
source using the cable
(44)
supplied.
2 - Connect the UPS input socket
(9)
to the
"UPS Input"
(55)
on the
HotSwap MBP
module, using the cable
(43)
supplied.
This cable and the connectors are marked
blue.
3 - Connect the UPS outlet
(8)
to the "UPS
Output"
(54)
on the
HotSwap MBP
module,
using the cable
(43)
supplied. This cable
and the connectors are marked red.
To power the
HotSwap MBP
module and
to connect it to the UPS, it is neccessary to
use the 10A FR/DIN cable kit for
HotSwap
MBP
(ref. 68439).
If the AC-power source socket is BS type,
use the 10A BS cable kit
HotSwap MBP
(ref. 68440).
4 - Connect the equipment to the outlets
(49)
and
(50)
on the
HotSwap MBP
module. These outlets differ, depending
on the version of the
HotSwap MBP
module.
Caution. Do not use UPS outlets (7) and (8) to supply equipment because use of switch (53) on the HotSwap MBP
module would cut supply to the equipment.
By-p
ass
Normal
UPS ON - OK to switch
BY
P
ASS SWITCH
56
55
49
HotSwap MBP
50
54
53
51 52
44
43
8
7
9