13 Technical data
28
ESR5-NV3-30
12/19 MN049010EN
www.eaton.com
Safety parameters for IEC 61508 - High Demand
SIL
3
PFH
d
1.8 x 10
-9
per hour
Diagnostic coverage (DC)
99 %
MTTF
d
63311 years
Demand rate
< 12 months
Proof test intervall
240 months
Duration of use
240 months
The specifications apply assuming the following calculation basis:
B
10d
400000 (at 3
A AC-15 DC-13)
Cycles
8760 per year
Safety characteristic data according to EN ISO 13849
Category
4
Performance Level
e
DC
avg
99 %
MTTF
d
124.23 years
CCF
passed
Duration of use
240 months
The specifications apply assuming the following calculation basis:
B
10d
400000 (at 3
A AC-15 DC-13)
Cycles
8760 per year