2 Description
6
ESR5-NO-21-24VAC-DC
12/19 MN049007EN
www.eaton.com
2 Description
The ESR5-NO-21-24VAC-DC safety relay can be used for emergency stop
and safety door monitoring as well as in safety circuits according to
EN
60204-1.
With this switching device, circuits are interrupted in a safety-oriented
manner.
Control is via a single channel or two channels, either with automatic or
manual start circuit (PSR-ESM4 only).
Depending on the external wiring, up to category
4, PL
e according to
EN
ISO
13849-1 or SILCL
3 according to EN
62061 can be achieved.
The safety relay is equipped with two enabling current paths and one signal-
ing current path that drop out without delay according to stop category
0.
Features
•
Emergency stop and safety door monitoring
•
Suitable up to category
4, PL
e (EN
ISO
13849-1), SILCL
3 (EN
62061)
•
Single-channel or two-channel wiring with cross-circuit detection
•
Automatic or manual start circuit
•
Plug-in screw terminal blocks