
Troubleshooting
Eaton ePDU G3 Troubleshooting Guide P-164000278—Rev 1
www.eaton.com/ePDU
19
2
215200
Eaton ePDU Input 2 Low Voltage Critical
The specified section voltage reading is less than the
value configured as the low voltage critical threshold.
2
215300
Eaton ePDU Input 2 High Voltage Warning
The specified section voltage reading is greater than
the value configured as the over voltage warning
threshold.
2
215400
Eaton ePDU Input 2 High Voltage Critical
The specified section voltage reading is greater than
the value configured as the over voltage critical
threshold.
2
216000
Eaton ePDU Input 2 Frequency OK
The frequency is not out of range.
2
216100
Eaton ePDU Input 2 Frequency out of +/- 3 Hz
tolerance
The frequency is out of range.
2
221000
Eaton ePDU Gang Phase Input Current No
Threshold
No section current threshold has been triggered.
2
221100
Eaton ePDU Gang Phase Low Current
Warning
The current amperage (A) reading for the specified
section is less than the value configured as the low
current warning alarm threshold.
2
221200
Eaton ePDU Gang Phase Low Current Critical
The current amperage (A) reading for the specified
section is less than the value configured as the low
current critical alarm threshold.
2
221300
Eaton ePDU Gang Phase Over Current
Warning
The specified section current amperage (A) reading is
greater than the value configured as the over current
warning threshold.
2
221400
Eaton ePDU Gang Phase Over Current Critical
The specified section input current amperage (A)
reading is greater than the value configured as the
over current critical alarm threshold.
2
222000
Eaton ePDU Gang Phase Voltage No
Threshold
No section voltage threshold has been triggered.
2
222100
Eaton ePDU Gang Phase Low Voltage
Warning
The specified section voltage reading is less than the
value configured as the low voltage warning
threshold.
2
222200
Eaton ePDU Gang Phase Low Voltage Critical
The specified section voltage reading is less than the
value configured as the low voltage critical threshold.
2
222300
Eaton ePDU Gang Phase Over Voltage
Warning
The specified section voltage reading is less than the
value configured as the over voltage warning
threshold.
2
222400
Eaton ePDU Gang Phase Over Voltage Critical
The specified section voltage reading is less than the
value configured as the over voltage critical
threshold.
2
223000
Eaton ePDU Gang Breaker Reset
No alarm has been triggered.
2
223100
Eaton ePDU Gang Breaker Tripped
An alarm has been triggered.
2
241000
Communication OK
No communication failure detected on Teridian
RS-485 bus
2
241100
Communication Lost
Communication failure detected on Teridian RS-485
bus
2
251000
Daisy Chain Communication OK
No communication failure detected on Daisy Chain
2
251100
Daisy Chain Communication Alarmed
Communication failure detected on Daisy Chain
2
231000
Eaton ePDU Outlet Current No Threshold
No outlet current threshold has been triggered.
Table 11. ePDU and User Alarms and Events (Continued)
Type Code
Identification and
Index Code
Alarm or Event
Description