background image

Warning - 
Intellectual Property Rights  

Eaton wishes to make it clear that it owns intellectual property rights in the 
product which it manufactures (whether or not listed in this leaflet) and that it 
will take legal action against any party found to be manufacturing, using, or 
selling any article which infringes the company’s intellectual property. All 
marks in this document identified with an R symbol or a TM symbol adjacent 
to the mark are trademarks of Eaton. 
 
 
© 2019 Eaton Electric Limited. 
All rights reserved.                                      www.eaton.com/recycling 

The use to which this product is put and its place of installation is outside our 
control. Particular care should therefore be taken to follow the instructions 
given here and to ensure their continued availability in conjunction with the 
use of the product. 
No responsibility can be accepted by us if these instructions are disregarded. 
Further copies of these instructions and information concerning the 
installation and proper use of this product can be obtained by contacting the: 

Technical Services Department 
Eaton Electric Limited, Middleton, Manchester, M24 1GQ. 
Tel: +44(0)8700 545 333, 
email: [email protected] 

M8 Cable Lug – 4 Qty 
rating as required  

M12 Contained Palm Width 

MCCB Cable Lug – 4 Qty 

M12 required for additional 

palm length.  

M12 Cable Lug – 4 Qty 

M12 required for 

additional palm length.  

Refer to main installation leaflet for additional fitting details (LT1222 400A -EM4PBK404, EM4PBK404M and LT1223 800A – EM4PBK804, EM4PBK804M) 

31mm 

16mm 

400A INCOMER METER KIT - EM4PBK404M 

Fit the ‘Live Side Connectors’ on top of the incoming M12 cable lugs 
and screw down onto the CT extension palms. Connect the Exel double 
insulated feed cables to the ‘Live side connectors’ using M8 cable lugs.  

400A INCOMER KIT - EM4PBK404 

Fit the ‘Live Side Connectors’ on top of the incoming M12 cable lugs 
and screw down onto the MCCB terminal. Connect the Exel double 
insulated feed cables to the ‘Live side connectors’ using M8 cable lugs.  

800A INCOMER KIT - EM4PBK804 

Fit the ‘Live Side Connectors’ on top of the incoming M12 cable lugs 
and screw down onto the extension palms. Connect the Exel double 
insulated feed cables to the ‘Live side connectors’ using M8 cable lugs.  

800A INCOMER METER KIT - EM4PBK804M 

Fit the ‘Live Side Connectors’ on top of the incoming M12 cable lugs 
and screw down onto the CT extension palms. Connect the Exel double 
insulated feed cables to the ‘Live side connectors’ using M8 cable lugs.  

M12 Cable Lug 
– 8 Qty 

16mm 

Live Side 
Connector 

Live Side 
Connector 

Live Side 
Connector 

M8 Cable Lug – 4 Qty 
rating as required  

M8 Cable Lug – 4 Qty 
rating as required  

Feed to 

Exel 

Feed to 

Exel 

Feed to 

Exel 

Feed to 

Exel 

15Nm 

31Nm 

31Nm 

31Nm 

15Nm 

46Nm 

46Nm 

15Nm 

M12 Cable Lug 
– 8 Qty 

Live Side 
Connector 

15Nm 

M8 Cable Lug – 4 Qty 
rating as required  

16mm 

16mm 