MEMSHIELD 4 INSTALLATION INSTRUCTIONS FOR 
EM4PBLSC LIVE SIDE CONNECTION  (up to 125A) 

Instruction leaflet LT1226 (02/19)

 

IMPORTANT NOTES 

1. This product should be installed, commissioned and maintained by or under the supervision of a competent electrician in                    
accordance with current electrical engineering Codes of Practice, Requirements for the Electrical Installations (IET Wiring 
Regulations BS7671), Construction (Design and Management) Regulations, HSG150 - Health and Safety in Construction, Statutory 
requirements and any Specific instruction issued by the Company. 
2. After completing the installation and testing of this product it is essential that this leaflet is drawn to the attention of the 
person responsible for its future operation and maintenance, and is at all times available for ready reference. 
3. These notes assume throughout that the product is disconnected from the supply. It is essential that this is done before any   
work is carried out. 
4. These Panelboards are only designed for use with Eaton MCCBs. Failure to comply will result in invalid warranty and 
certification. 

Items Supplied in Live Side Connection Kit 

M8 x 16mm Hex Head Bolt DIN934 Grade 8.8 

                    4 Qty 

M8 CONICAL SPRINGWASHER DIN6796                                                         4 Qty 
Copper Connectors - 25 x 3mm 

 

                    4 Qty 

Caution Label   

 

 

                    1 Qty 

 

Items required for Live Side Connection  

Double Insulated Cable – length and rating  as required                           4 Qty      – To feed the Exel 2 
M8 Cable Lugs - rating as required  

 

                    4 Qty      – To connect the live side connector 

Cable Ferrule - rating as required  

 

                    4 Qty      – To connect the cable to the Exel 2.  

Exel 2 – TPN Fuse Switch Disconnector – Rating as required                     1 Qty      – Eaton list numbers   -  

 

M12 Incomer Cable lugs – See Incomer type for Lugs required (Page 2).  

LIVE SIDE CONNECTION  - GENERAL ARRAGEMENT  - UP TO 125A 

A live side connection, off the incoming MCCB, can be fitted using the supplied copper connectors. 
Double insulated cable is used to feed an Exel 2 TPN Fuse Switch disconnector enclosure.  

live side copper 
connector 

Exel 2 TPN Fuse Switch 
Disconnector. 
Padlockable in ON or 
Off position. 

Panelboard 

Double Insulated Cable 

Live side Connection 

20A TPN   

- 15KXTNC2F 

32A TPN  

- 30KXTNC2F 

63A TPN   

- 60KXTNC2F 

100A TPN   

- 100KXTNC2F 

125A TPN   

- 125KXTNC2F 

Caution Label - fitted on the Exel enclosure 

CAUTION 

FED FROM LIVE SIDE 

OF PANELBOARD 

INCOMER 