614-06817-00
Technical characteristics
Performances tested according to IEC 61643-1 (class 3) standard for 8/20 µs surge wave
(*) Warning:
Output cables should not exceed 10 m length.
Ellipse PRO
650
850
1200
1600
•
UPS
power
650 VA /
400 W
850 VA /
510 W
1200 VA /
750 W
1600 VA /
1000 W
• Nominal input voltage
165 V - 264 V, adjustable to 150 V - 284 V
•
Input frequency
50/60 Hz (46 - 70 Hz working range)
•
Voltage/frequency of battery backup
outlets
19
in battery mode
220 V / 230 V / 240 V +15 % -20 % (50/60 Hz ± 1 Hz)
•
Total output current for all outlets
10 A max
•
Output current of battery backup
outlets
19
3 A max
3.6 A max
5.5 A max
7.3 A max
•
Leakage current
0.4 mA
•
Input protection
10 A resettable circuit breaker
•
Transfer time
5 ms typical
•
Telephone/Data surge protection
Tel, ISDN, ADSL, Ethernet
•
Sealed lead-acid battery
12 V, 7 Ah
12 V, 9 Ah
2x12V, 7 Ah
2x12V, 9 Ah
•
Automatic battery test
Once a week
•
Average battery life
4 years typical, depending on temperature and number of discharge
cycles
•
Operating temperature
0 to 35 °C
•
Storage temperature
-25 °C to +55 °C
•
Operating relative humidity
0 to 85 %
•
Operating elevation
0 to 2000 m
•
Safety standards
IEC 62040-1, CE certified
•
Electromagnetic compatibility standards
IEC 62040-2, C1*
•
Warranty
3 years
•
Dimensions (mm/
inch
)
260 x 82 x 285 /
10.24 x 3.23 x 11.22
275 x 82 x 390 /
10.83 x 3.23 x 15.35
•
Weigth (kg/
lb
)
6.9 /
15.2
7.3 /
16.1
9.7 /
21.4
11.5 /
25.4
AC input source protection, Ellipse PRO:
650
850
1200
1600
•
Uoc (common mode / differential mode)
6 kV / 2 kV
•
Up (common mode / differential mode)
1.5 kV / 1 kV
•
In
3 kA
Dielectric isolation
•
AC Ground
1500 Vac, 50 Hz
•
AC / TEL
3000 Vac, 50 Hz
•
Tel / Ground
1000 Vac, 50 Hz
Temporary overvoltage (TOV)
•
Uc
250 Vac
•
Ut
430 Vac
Energy dissipation
405 Joules
Summary of Contents for Ellipse PRO 1200 FR