Conventional Fire System

Eaton Conventional Fire Panel

EFCV8ZONE

User Manual

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for EFCV8ZONE

Page 1: ...Conventional Fire System Eaton Conventional Fire Panel EFCV8ZONE User Manual www acornfiresecurity com www acornfiresecurity com...

Page 2: ...ion 6 4 2 What To Do In The Event Of A Fault Condition 6 4 3 What To Do When Re Enabling Zones With Latching Detect 6 5 ROUTINE TESTING 7 5 1 Daily Testing Premises Management 7 5 2 Weekly Testing Pre...

Page 3: ...for the site must ensure that all users of the system have read this manual and are trained on its use 1 2 Definitions Premises Management Is a delegated person or persons with specialist knowledge a...

Page 4: ...r and the appropriate fault indicator refer to 8 for more details The panel buzzer will sound a slow pulsing tone 2 System Fault Severe failure of the panel the service company must be contacted immed...

Page 5: ...Management only and is protected by an access code The following functions are available for this level Silence Fire Alarm Devices Sound Fire Alarm Devices Reset System Mute Buzzer Enable Disable Zone...

Page 6: ...When it is safe to do so silence the fire alarm devices and reset the system Note the time the fire alarm occurred and log the fire event in the log book If the fire alarm was a false activation i e t...

Page 7: ...refer to 6 7 for more details Record the weekly test results in the log book IT IS THE RESPONSIBILITY OF THE PREMISES MANAGEMENT TO DEFINE A FIXED DAY AND TIME OF WEEK THAT THE WEEKLY TEST IS PERFORME...

Page 8: ...p sounding the panel buzzer will continue sounding This function will immediately exit back to Access Level 1 6 3 Sound Fire Alarm Devices This function is only available at access level 2 and when th...

Page 9: ...ction will allow the following to be disabled Individual Zones All fire alarm devices FRE if fitted FPE if fitted Enter the access code 3112 Press the Disable Enable button 1 All previous disablements...

Page 10: ...indicator will also remain lit When a fire detection device or manual call point is activated in the zone under test it will sound all fire alarm devices for 3 seconds and then will automatically sile...

Page 11: ...Detectors Detectors 1 Reception 2 1 2 Office 1 1 2 3 Office 2 3 2 4 Kitchen 2 1 5 6 7 8 A brief description of where the zone is on the site and or what rooms are in the zone Quantities of each device...

Page 12: ...1 YES NO Auxiliary Relay 2 YES NO Auxiliary Relay 3 YES NO Auxiliary Relay 4 YES NO Auxiliary Relay 5 YES NO Auxiliary Relay 6 YES NO Auxiliary Relay 7 YES NO Auxiliary Relay 8 YES NO Circled if conne...

Page 13: ...book are maintenance work false alarms in accordance with BS5839 part 1 and any other event this includes genuine fires and faults SITE DETAILS Premises Management Names Mr P Manager Company Name of P...

Page 14: ...ompetent Person at a maintenance visit if required UNWANTED FALSE FIRES Date Time Zone Cause if Maintenance Maintenance Category Further Signed Location Known Visit Needed Findings Further Action YES...

Page 15: ...Charger Fault ON ON ON SLOW Charger voltage fault Sounder Fault ON ON SLOW SLOW Short or Open circuit condition on the sounder circuit FRE Fault ON ON SLOW SLOW Short or Open circuit condition on the...

Page 16: ...www acornfiresecurity com www acornfiresecurity com...