EC500 Controller Handbook
Copyright © 2019 Eaton Corporation. All Rights Reserved.
Issue A March 2019
Page 68 of 107
Parameter
Description
Default Value
Where to find:
DCIF to be installed (1
–
4), configure
install status.
DCIF
n
:
Installed
/
Not Installed
Please note that DCIF 1 must always be
installed as Bus Voltage is read from
DCIF 1. Refer section DC Interface
Boards on page 8 for more wiring
details.
DCIF 3:
Not Installed
DCIF 4:
Not Installed
PFC IO 8
DCIF 4V2C, DCIF 6V7C and DCIO 6V3C
support 8 PFC Input & Output Board.
Select PFC IO 8 as
Installed
or
Not
Installed
as per system configuration.
Wrong selection will cause non-
availability or wrong mapping of PFC
Inputs and outputs in hardware.
Installed
PFC IO 16
–
1
PFC IO 16
–
2
EC500 supports 2 number of PFC IO 16
boards in addition to PFC IO8. These
boards are installed on CAN bus
directly. Select PFC IO 16 (1/2) as
Installed
or
Not Installed
as per system
configuration. Wrong selection will
cause non-availability or wrong
mapping of PFC Inputs and outputs in
hardware.
Refer section PFC Boards on page 8 for
more details.
Not Installed
Solar Chargers
If Solar chargers are to be installed,
enable Solar Functionality. Select
Installed
or
Not Installed
.
Solar alarms, solar charger control &
monitoring will be done only when this
parameter is set to
Installed
. More
settings will be enabled when set to
Installed
.
Not Installed
Modem
EC500 supports GSM / GPRS modem
board. Modem functionality is enabled
when Modem is
Installed
. When
Not
Installed
all settings and alarms are
suppressed / hidden.
Not Installed
DG Control
If control for external DG start / stop is
required,
Enable
this control.
Disabled
The maximum number of PFC Inputs & Outputs supported is 40.
Refer section Generator Control on page 53 for more settings and details on DG Control.
BATTERY CONFIGURATION
The following battery settings must be configured.