2

Battery Upgrade Instructions for 9355 (20–30 kVA)

—Rev 01

Figure 3. Wiring Harness Adapter P-152001881

The total battery string voltage in a 9355 20-30 kVA UPS is 216V (18 batteries, where is each battery is 12V
nominal). The single-tray configuration that is being replaced holds 18 batteries. Two strings fit in each battery
shelf of the 9355 20-30 kVA UPS. The single-tray red connector is the most positive connection while the black
is the negative connection. The white connector presents the middle point in the single-tray configuration,
where 108V is measured from the white to the red and 108V from the white to the black. The white connector
is used for CSE testing only.

The replacement tray sets contain nine batteries each, such that it takes two trays to complete one string.

Each P-106000220 kit includes two single-row battery trays and two harness adapters. Only one harness
adapter is needed for the installation; the second harness adapter is a spare.

Introduction

Summary of Contents for Eaton series

Page 1: ...Revision 01 Battery Upgrade Instructions For use with the Eaton 9355 20 30 kVA Eaton Series...

Page 2: ...his manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries Please read all instructions before operating the equipment and save this...

Page 3: ...20 30 kVA Rev 01 iii T Ta ab blle e o of f C Co on nt te en nt ts s 1 1 I In nt tr ro od du uc ct tiio on n 1 1 2 2 B Ba at tt te er ry y U Up pg gr ra ad de e P Pr ro oc ce ed du ur re e 3 3 2 1 Com...

Page 4: ...iv Battery Upgrade Instructions for 9355 20 30 kVA Rev 01 Table of Contents...

Page 5: ...existing two row battery tray assembly with two single row battery assemblies with two circuit connectors Along with an adapter harness it is permanently installed in the UPS to convert from single ci...

Page 6: ...the most positive connection while the black is the negative connection The white connector presents the middle point in the single tray configuration where 108V is measured from the white to the red...

Page 7: ...erformed by qualified personnel 1 Remove the 9355 20 30kVA front door see Figure 4 Figure 4 Remove the UPS Front Door IMPORTANT In the event of input power failure while performing this procedure batt...

Page 8: ...and Remove the Battery Dead Front 5 As shown in Figure 6 disconnect the positive red and negative black battery connectors for all the battery trays NOTE If an external battery cabinet is attached it...

Page 9: ...nected before proceeding 6 Remove the two M5 bolts that secure the retaining bracket on the battery shelf for the battery tray to be replaced see Figure 7 Figure 7 Remove the Battery Retaining Bracket...

Page 10: ...ys are now side by side with one old dual row tray on the same shelf forming two battery strings see Figure 9 Figure 9 Slide Two Single Row Battery Trays into Place 9 Re install the battery retaining...

Page 11: ...adapter to the UPS battery harness red to red and black to black WARNING It is critical that these connections are correct A harmful arc flash will occur if these connections are crossed Figure 11 In...

Page 12: ...e 13 Figure 13 Anchor Battery Harness to Battery Retaining Bracket CAUTION Observe proper precautions when verifying polarity It is recommended that polarity checks are performed by qualified personne...

Page 13: ...first then make all black connections 17 Re install the battery cover panel dead front using the thirteen M5 bolts removed in Step 4 NOTE If an external battery cabinet is attached reconnect it to the...

Page 14: ...01 01...

Reviews: