ES, Emergency-stop
371
02/16 MN05013001Z EN
ES, Emergency-stop
The emergency-stop function block is used for the safety-
related single or two-channel monitoring of emergency-stop
circuits. This enables the safe stopping of a hazardous move-
ment if the immediate disconnection of the power supply
does not cause hazardous states.
easySafety enables the monitoring of up to 14 single-
channel emergency-stop circuits or 7 two-channel emer-
gency-stop circuits.
Function block
Figure 185:
Emergency-stop function block
a
Coils ES..I1 and ES..I2: Monitoring of the 1 or 2-channel emer-
gency-stop switch.
Use only in the safety circuit diagram.
b
Coil ES..RE: Reset of the function block to Manual Start (MST)
and Controlled Start (CST) modes and starting of normal oper-
ation.
Use only in the safety circuit diagram.
c
Coil ES..EN: Selective activation or deactivation of the function
block function (optional).
Optional use either in the safety or standard circuit diagram.
I1
I2
RE
EN
>DT
ER
DG:
QV:
ES...
Emergency Stop
QS
DW
a
b
c
d
e
f
g
h