45
Transfer time
Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of utility)
Power factor
1
Load crest ratio
3 to 1
* for 208V output, the load level will be derating to 90%.
Table 7. Electrical output connections
Model
Output connection
Output cable
Eaton DX RT 6000VAIN
Hardwired
Not provided
Eaton DX RT 6000VAXLIN
Eaton DX RT 10000VAIN
Eaton DX RT 10000VAXLIN
Table 8. Environmental and safety
Certifications
EN 62040-1
IEC/EN 62040-2: Cat. C3
IEC/EN 62040-3
EN 60950-1
EMC (Emissions)*
Conduction: C3 IEC/EN 62040-2
Radiation: C3 IEC/EN 62040-2
EMC (Immunity)
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on signal ports) IEC
61000-4-5, Level 4, Criteria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4
IEC 61000-4-11
* for output cable < 10m.
Agency markings
CE
Operating temperature
0~40
℃
full load no derating
40~50
℃
output power derating to 50% load, Charger
current derating 50%
Storage temperature
-15 to 40°C (32 to 104°F) with batteries
-25 to 60°C (5 to 140°F) without batteries
Transit temperature
-25 to 55°C (-13 to 130°F)
Relative humidity
0 to 95% no condensing