4 Commissioning
4.10 Status words
54
DX-NET-PROFINET2-2
01/22 MN040062EN
www.eaton.com
4.10.1 Simplified start with the PROFIdrive profile
Use the following settings (as hexadecimal values) for the control word (out-
put bytes 0 and 1):
Table 23:
Starting
Table 24:
Stop with ramp
Table 25:
Coast stop
Table 26:
Fault scenario
Value
Description
16#0000
Voltage present on device and connection.
16#047E
The variable frequency drive/variable speed starter switches to the “ready” status, however it
is still stationary.
16#047F
The variable frequency drive/variable speed starter switches from the “ready”status to the
RUN status and starts if a setpoint has been specified.
Value
Description
16#047F
The variable frequency drive/variable speed starter is in operation.
16#046F
The variable frequency drive/variable speed starter executes the ramp stop.
16#047F
The ramp stop is canceled and the variable frequency drive/variable speed starter continues to
run.
Value
Description
16#047F
The variable frequency drive/variable speed starter is in operation.
16#047E
The variable frequency drive/variable speed starter executes the coast stop.
16#047F
The ramp stop is canceled and the variable frequency drive/variable speed starter continues to
run.
Value
Description
16#047F
A fault occurs during ongoing operation.
16#0507
The variable frequency drive/variable speed starter is reset.
16#047F
The variable frequency drive/variable speed starter starts after troubleshooting.