8 SmartWire-DT
8.10 SmartWire-DT diagnostics
212
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
8.10.2 Advanced SmartWire-DT diagnostics
When there is a collective diagnostic (input byte 0, bit 4 (DIAG)), the
DS7-SWD soft starter will provide advanced diagnostic messages:
Motor-protective circuit-breaker diagnostic messages (profiles 1 to 9)
The following are the messages generated by the PKE motor-protective
circuit-breaker:
Table 42: PKE motor-protective circuit-breaker diagnostic messages
Soft starter diagnostic messages (profiles 1 to 11)
The following are the messages generated by the DS7-SWD soft starter:
Table 43: DS7-SWD soft starter diagnostic messages
Diagnostic alarm 15
hex
If the 1-0-A switch does not assume a clear position for longer than
4 seconds, the DS7-SWD soft starter will be switched off and generate
the following error messages:
•
DIAG,
•
ERR (only profiles 4 to 11),
•
Diagnostic alarm 15
hex
(
In addition, the module’s SmartWire-DT diagnostic LED will flash green
(frequency: 3 Hz).
Value
[hex]
Meaning
Remedy
Notes
3
No communication
Between DS7-SWD soft
starter and PKE trip block
Check whether the PKE trip block
being used is a PKEXTUA-… trip
block.
Check the PKE32-COM
connections and reconnect the
device if necessary.
The DS7-SWD can continue to be
used in this state. The main circuits
are isolated by the PKE in the event
of an overload.
In these cases, an enabled overload
function (ZMR) will not have any
effect.
Value
[hex]
Meaning
Remedy
Notes
14
Internal communication
problem in soft starter
• If the error continues, switch
the supply voltage off/on
• Check EMC
• Replace soft starter
–
15
no unambiguous position
of the 1-0-A switch for
more than 4 seconds
Move the 1-0-A switch to one of
the three defined positions.
Value 00
hex
is signaled using input
byte 0, bits 2 and 3.
For more information, see below.
19
There is a DS7-SWD
soft starter warning.
Read warning PNU 860.0 and fix
the cause
Corresponds to the WARN bit in the
corresponding input byte
1A
There is a DS7-SWD
soft starter fault.
• Read fault PNU 944 to
PNU 952
• Fix the fault and
acknowledge the error
message
Corresponds to the ERR bit in the
corresponding input byte
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...