8 SmartWire-DT
8.9 Programming
DS7 Soft starter
09/16 MN03901001Z-EN
www.eaton.com
161
8.9.3.2 Inputs (status) profiles 1, 2, 3
Profiles 1, 2, and 3 have a maximum of five input bytes and one output byte.
Byte 0:
Status information: DS7, PKE, PKE-SWD-32
→
DS7-SWD soft starters can also be operated, without a PKE
motor-protective circuit-breaker, with a PKZ or an NZM as a
safety device.
→
For additional information on how to connect a DS7-SWD to a
PKE motor-protective circuit-breaker with a trip block, consult
manual MN05006001Z-EN, “SmartWire-DT Modules.”
→
The number of cyclic input bytes can be changed with the
module’s different profiles (
7
6
5
4
3
2
1
0
SUBST
PRSNT
–
DIAG
A2
A1
P
C
Data bit
Designation
Meaning
0
DS7 run
0: Stop soft starter DS7-SWD
1: Run DS7-SWD soft starter
1
STAT (PKE)
0: PKE tripped
1: PKE Powered up
2, 3
A1, A2
1-0-A switch on DS7-SWD soft starter:
00: not defined
10: Position A: Automatic
(commands via SmartWire-DT/terminal)
01: Position 0: DS7 stop
11: Position 1: DS7 operation
4
DIAG
Soft starter diagnostics:
0: no diagnostic alarm
1: Diagnostic alarm present
5
–
Not used
6
PRSNT
Presence of DS7-SWD soft starter:
0: Device not present
1: Device present
7
SUBST
Presence of a universal module:
0: Configured module present
1: universal module M22-SWD-NOP(C) present
Summary of Contents for DS7 Series
Page 1: ...Manual DS7 Soft starter 09 16 MN03901001Z EN...
Page 4: ...II...
Page 36: ...1 Device series DS7 1 14 Function 32 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 96: ...3 Installation 3 6 Insulation test 92 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...
Page 188: ...8 SmartWire DT 8 9 Programming 184 DS7 Soft starter 09 16 MN03901001Z EN www eaton com...