Cautions, Warnings and Instructions
Wiring Warnings for Electrical Practices and Wire Sizes
The Cautions, Warnings, and instructions in this section summarize the
procedures necessary to ensure a soft starter installation complies with
Underwriters Laboratories
®
guidelines.
Terminal Tightening Torque and Wire Size
The wire size range and tightening torque for field wiring terminals are
presented in the table below.
Motor Overload Protection
Soft starter DS7 requires against thermal overload an combination with an
overload relay (PKZ, PKE) or a bimetallic relay (ZB).
If two or more motors are connected behind the soft starter, each engine must
be separately protected against thermal overload.
Circuit Breaker and Fuse Sizes
The soft starter connections to input power must include UL Listed inverse time
circuit breakers with 600 V rating, or UL Listed fuses as shown in the table
below.
NOTICE
UL/CSA = Cu only, Ampacity per 75 °C Table.
NOTICE
Open Type Equipment.
NOTICE
Each motor must be protected against thermal overload.
Wire size
Torque
Model Types
Power
Control
Power
Control
1x
2x
1x
2x
AWG
mm
2
AWG
mm
2
AWG
mm
2
AWG
mm
2
Nm
lb-in
Nm
lb-in
DS7-340SX016N0-N
DS7-340SX024N0-N
DS7-340SX032N0-N
18 - 6
0.75 - 16
18 - 6
0.75 - 3.5
18 - 14
0.5 - 2.5
18 - 16
0.5 - 1.0
3.2
28.32
0.6
5.31
DS7-342SX016N0-N
DS7-342SX024N0-N
DS7-342SX032N0-N
18 - 6
0.75 - 16
18 - 6
0.75 - 3.5
18 - 14
0.5 - 2.5
18 - 16
0.5 - 1.0
3.2
28.32
0.6
5.31
→
AWG = American Wire Gauge. Smaller numbers represent increasing wire thickness.
MCM/kcmil = 1,000 circular mils, a measure of wire cross-sectional area
mm
2
= square millimeters, a measure of wire cross-sectional area
NOTICE
Suitable for use on a circuit capable of delivering not more than
5,000 rms symmetrical ampers, 480 V maximum.
Model Types
SC Ratings
Branch Circuit Protection
Max. HP [V AC]
Max. kW [V AC]
200
240
480
230
400
DS7-340SX016N0-N
DS7-342SX016N0-N
5 KA, 480 V AC
100 A RK5 fuse or breaker
3
5
10
4
7.5
DS7-340SX024N0-N
DS7-342SX024N0-N
5 KA, 480 V AC
100 A RK5 fuse or breaker
7.5
5
15
5.5
11
DS7-340SX032N0-N
DS7-342SX032N0-N
5 KA, 480 V AC
125 A RK5 fuse or breaker
10
10
25
7.5
15