82
Instruction Booklet
IB 33-790-1J
Effective November 2010
Instructions for Low Voltage Power
Circuit Breakers Types DS and DSL
EaToN CorPoraTIoN www.eaton.com
Section 13 - Renewal Parts
13.0 GENERAL
Renewal Parts Data, listing by name and style number
the recommended renewal parts to be kept in stock, are
supplied separate from this book. When ordering parts,
always specify the part name and style number, if known,
from the Renewal Parts Data, RP.22B.01.T.E. If the style
number is not known, refer to the Figure number, name
and item number as shown in this book, along with the
breaker type and shop order number or style number as
shown on the nameplate on the front cover of the circuit
breaker.
Some of the detail parts shown in the figures in this book
will be available only as part of a sub-assembly. The
detail parts in the figures are illustrated to show their
function and location in the assembly; but certain parts,
due to manufacturing procedures or installation proce-
dures, are recommended and furnished as part of a sub-
assembly. The renewal parts data indicates which parts
are available as individual items or in a sub-assembly.
When inquiring about or ordering parts, refer to the fig-
ures in this book and the renewal parts data for identifica-
tion of the part or sub-assembly in question.
13.1 IDENTIFYING PARTS FOR DS-416S AND
DS-206S
13.1.1 DS-416S Parts
The parts of a DS-416S are almost identical to those of a
DS-420. The parts shown in a proper DS-420 figure (or
drawing) are used for the same purpose in Type
DS-416S. Description of these parts are the same too,
but they are identified as parts for DS-416S (or shop
order number).
13.1.2 DS-206S Parts
The parts of Type DS-206S are very similar to those of
DS-206. By reference to the proper DS-206 figure (or
drawing) identification of their common parts can be
made. When they are ordered for the DS-206S, it is so
specified. The major differences are:
1. DS-206S uses the three piece base of the DS-416,
instead of the one piece molded base of the DS-206;
2. DS-206S uses the DS-416 arc chute;
3. DS-206S main disconnects have 50% more fingers
than the DS-206;
4. DS-206S has twice as many contacts and arms as
the DS-206; and
5. The pole unit hinge of DS-206S is a forked construc-
tion or a miniature version of the DS-416 hinge.