EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
High Level Menus
NOTE: Not all buttons are available on all versions of firmware. Those shown below are for
3.03.53 (PH2
– 2016)
Fig 31
Buzzer Disabled / Enabled
The Buzzer can be permanently disabled using this feature, a disabled led will be displayed on the
panel and when interrogating the disable devices in the user menu, this will be shown as one I/O
disabled.
Enable / Disable all Outputs
This menu enables the engineer to carry out a full test without any outputs operating. This function
cannot be used with Weekly or Walk test features.
The outputs can be switched on and off from this menu, if however, the outputs are inadvertently left
disabled when the engineer leaves site, the user can re-enable the outputs from the enable/disable
menu in 2214, or on later versions simply toggle the button in the high level menu.