5

Instruction Manual 

IM01005016E

Effective January 2014

CVX050/100 Surge Protective Device 

Installation and Operation

 

EATON 

www.eaton.com

Before installation as  SPDe:
2.4  Wiring, for DC Units. 

Step A:

Verify system voltage does not exceed maximum suggested operat-

ing voltage listed in table.

• 

All voltage measurements should be completed with a DC volt-

meter.

• 

DO NOT INSTALL SUPPRESSOR IF MEASURED VOLTAGE 

EXCEEDS MAXIMUM SUGGESTED OPERATING LIMITS.

Maximum Suggested Operating Voltages and Wire Colors

Model 

Number

Line to 

Line

Line to 

Ground

(+) 

Wire Color

(-) 

Wire Color

Ground 

Wire Color

CVX050-048DC 130

65

Red

Black

Green

CVX100-125DC 288

144

Red

Black

Green

Step B:

Choose suppressor installation location so leads are kept as short 

and straight as possible. 

SUPPRESSOR MUST BE CONNECTED 

TO ELECTRICAL SYSTEM VIA ONE OF THE FOLLOWING CIRCUIT 

INTERRUPT DEVICESe:

• 

1-Double Pole/Single Throw 30 Amp Circuit Breaker NOTE:  Pre-

existing breakers of rated load size may be utilized if provisions 

for multi-conductor connections are made according to N.E.C.110-

14A.

• 

2-Single Pole/Single Throw 30 Amp Circuit Breakers

• 

2-30 Amp Class RK5 Fuse(s) (Such as Bussmann FRN-R-30 for 

less than 125 VDC)

Ground

Circuit

Interrupt

Device

SPD

Direct Current (DC)

48V, 125V

Power

Supply

(+)

(-)

Before Installation as Secondary Surge Arrestore:

Step A:

Follow 2.4 Wiring, for DC Units.  Step A.

Step B:

No circuit interrupt device is required.

Installation Instructions as SPDe:

Step 1:

REMOVE POWER FROM ELECTRICAL SYSTEM BEFORE 

INSTALLING SUPPRESSOR.

Step 2:

Mechanically mount suppressor:

• 

Suppressor to be installed through panel knockout and via sup-

pressor optional (these are not  on  this  unit)mounting feet. Place 

suppressor against mounting surface and mark feet positions if 

applicable. Complete conduit connection installation. Screw box to 

surface with appropriate screws.

• 

Assure weatherproof conduit and fittings are used to maintain 

NEMA 4 rating.

• 

Suppressor to be mounted for shortest and straightest possible 

wire installation from suppressor to system bus. Excessive wire 

length and sharp bends degrade suppressor performance; there-

fore, avoid excessive wire length and sharp bends when at all 

possible. 

• 

If installing on a system other than electrical panel, mount in close 

proximity to system being protected using necessary means for 

mounting.

otee:

N

A CIRCUIT INTERRUPT DEVICE IS STILL REQUIRED WHEN 

INSTALLING SUPPRESSOR ON A SYSTEM OTHER THAN ELECTRICAL 

PANEL.

• 

Suppressor contains no position-oriented components and can be 

mounted upside down or sideways. 

Step 3:

Wire suppressor into electrical system:

• 

Cut wire(s) as short as possible for optimum suppressor perfor-

mance.

• 

Connect GROUND (Green) wire to system ground bus bar. 

• 

Connect Red wire to “+” and Black wire to “-”.

Step 4:

Apply power to system.  Indicator light should glow.  If light does not 

glow, remove power and contact supplier.  

Installation Instructions as Secondary Surge Arrestore: 

Step 1:

Follow steps 1 through 4 above, only circuit interrupt device not 

required.

Summary of Contents for CVX050

Page 1: ...sedes IM01005016E Rev 4 Rev 5 Instruction Manual IM01005016E CVX050 100 Surge Protective Device Installation and Operation Contents Description Page 1 Introduction 2 2 Installation 3 3 Specifications...

Page 2: ...H THE SPD CONNECTED TO THE ELECTRICAL SYSTEM FAILURE TO DISCONNECT THE SPD DURING A HIGH POT TEST WILL RESULT IN DAMAGE TO THE SPD AFTER INSTALLATION THIS DEVICE IS NOT REPAIRABLE AND CONTAINS NO SERV...

Page 3: ...DEVICE SEE WARNING LABEL DANGER HIGH VOLTAGE Suppression Circuit Status 1 LED per phase normally on OK CVX050 Phase Ground Neutral Wires Drill or punch a 7 8 hole in wall of electrical panel Number a...

Page 4: ...connection 3 Connect the SPD s neutral wire white to the system s neu tral connection not required for 3 phase delta systems 240D 480D 600D 4 Connect the SPD s phase A B and C wires black to the sys t...

Page 5: ...required Installation Instructions as SPD Step 1 REMOVE POWER FROM ELECTRICAL SYSTEM BEFORE INSTALLING SUPPRESSOR Step 2 Mechanically mount suppressor Suppressor to be installed through panel knockout...

Page 6: ...ach phase voltage being monitored see Figure 4 1 Single phase and DC electrical systems will light only one LED split phase systems light two LEDs while three phase systems light all three If the conn...

Page 7: ...ument may be reproduced in any way without the express written approval of Eaton Specifications contained herein are subject to change without notice EATON CONFIDENTIAL AND PROPRIETARY NOTICE TO PERSO...

Page 8: ...com 2014 Eaton All Rights Reserved Printed in USA Publication No IM01005016E TBG000625 January 2014 Eaton is a registered trademark All other trademarks are property of their respective owners Instru...

Reviews: