LCX9000 Liquid-Cooled Drives User Manual
MN04005001E
For more information visit:
www.EatonElectrical.com
3-5
January 2007
Fuse Sizes, Drives
The fuse sizing in the tables below is based on Bussman aR fuses. We recommend use of
these fuses. Sufficient protection against short circuit cannot be guaranteed if other fuse
types are used.
Table 3-5: Fuse Sizes for LCX9000 Liquid-Cooled (500V) Drives
Tj = 77°F (25°C).
SHT fuses can be assembled into DIN fuse base of the corresponding size.
Note:
Data in italic refer to drives with 12-pulse supply.
Chassis
Catalog
Number
I
th
(A)
DIN43620
DIN43653 (80 mm)
DIN43653 (110 mm)
Fuse
U
n
(V)
Fuse
I
n
(A)
Qty. of
Fuses per
Phase 3~
aR Fuse
Part No.
Fuse
Size
aR Fuse
Part No.
Fuse
Size
aR Fuse
Part No.
Fuse
Size
CH3
LCX016A0-4
16 170M1565 DIN000 170M1415 000T/80
—
—
690
63 1
LCX022A0-4
22 170M1565 DIN000 170M1415 000T/80
—
—
690
63 1
LCX031A0-4
31 170M1565 DIN000 170M1415 000T/80
—
—
690
63 1
LCX038A0-4
38 170M1565 DIN000 170M1415 000T/80
—
—
690
63 1
LCX045A0-4
45 170M1567 DIN000 170M1417 000T/80
—
—
690
100 1
LCX061A0-4
61 170M1567 DIN000 170M1417 000T/80
—
—
690
100 1
CH4
LCX072A0-4
72 170M3815 DIN1
170M3065 1xTN/80 170M3215 1xTN/110 690
200 1
LCX087A0-4
87 170M3815 DIN1
170M3065 1xTN/80 170M3215 1xTN/110 690
200 1
LCX105A0-4
105 170M3815 DIN1
170M3065 1xTN/80 170M3215 1xTN/110 690
200 1
LCX140A0-4
140 170M3815 DIN1
170M3065 1xTN/80 170M3215 1xTN/110 690
200 1
CH5
LCX168A0-4
168 170M3819 DIN1
170M3069 1xTN/80 170M3219 1xTN/110 690
400 1
LCX205A0-4
205 170M3819 DIN1
170M3069 1xTN/80 170M3219 1xTN/110 690
400 1
LCX261A0-4
261 170M3819 DIN1
170M3069 1xTN/80 170M3219 1xTN/110 690
400 1
CH61
LCX300A0-4
300 170M5813 DIN2
170M5063 2TN/80
170M5213 2TN/110
690
700 1
LCX385A0-4
385 170M5813 DIN2
170M5063 2TN/80
170M5213 2TN/110
690
700 1
CH72
LCX460A0-4
460 170M6814 DIN3
170M6064 3TN/80
170M6214 3TN/110
690
1000 1
LCX460A0-4
460 170M5813 DIN2
170M5063 2TN/80
170M5213 2TN/110
690
700 2
LCX520A0-4
520 170M6814 DIN3
170M6064 3TN/80
170M6214 3TN/110
690
1000 1
LCX520A0-4
520 170M5813 DIN2
170M5063 2TN/80
170M5213 2TN/110
690
700 2
LCX590A0-4
590 170M6814 DIN3
170M6064 3TN/80
170M6214 3TN/110
690
1000 1
LCX590A0-4
590 170M5813 DIN2
170M5063 2TN/80
170M5213 2TN/110
690
700 2
LCX650A0-4
650 170M8547 3SHT
170M6066 3TN/80
170M6216 3TN/110
690
1250 1
LCX650A0-4
650 170M5813 DIN2
170M5063 2TN/80
170M5213 2TN/110
690
700 2
LCX730A0-4
730 170M8547 3SHT
170M6066 3TN/80
170M6216 3TN/110
690
1250 1
LCX730A0-4
730 170M5813 DIN2
170M5063 2TN/80
170M5213 2TN/110
690
700 2
CH63
LCX820A0-4
820 170M6812 DIN3
170M6062 3TN/80
170M6212 3TN/110
690
800 2
LCX920A0-4
920 170M6812 DIN3
170M6062 3TN/80
170M6212 3TN/110
690
800 2
LCXH10A0-4
1030 170M6814 DIN3
170M6064 3TN/80
170M6214 3TN/110
690
1000 2
LCXH11A0-4
1150 170M6814 DIN3
170M6064 3TN/80
170M6214 3TN/110
690
1000 2
CH74
LCXH13A0-4
1370 170M6814 DIN3
170M6064 3TN/80
170M6214 3TN/110
690
1000 3
LCXH13A0-4
1370 170M6812 DIN3
170M6062 3TN/80
170M6212 3TN/110
690
800 2
LCXH16A0-4
1640 170M6814 DIN3
170M6064 3TN/80
170M6214 3TN/110
690
1000 3
LCXH16A0-4
1640 170M6812 DIN3
170M6062 3TN/80
170M6212 3TN/110
690
800 4
LCXH20A0-4
2060 170M8547 3SHT
170M6066 3TN/80
170M6216 3TN/110
690
1250 3
LCXH20A0-4
2060 170M6814 DIN3
170M6064 3TN/80
170M6214 3TN/110
690
1000 4
LCXH23A0-4
2300 170M8547 3SHT
170M6066 3TN/80
170M6216 3TN/110
690
1250 3
LCXH23A0-4
2300 170M6814 DIN3
170M6064 3TN/80
170M6214 3TN/110
690
1000 4