IN ORDER TO AVOID ELECTRIC SHOCK OR OTHER POSSIBLE INJURY:

•  DO NOT USE THIS PRODUCT FOR HUMAN SAFETY APPLICATIONS. 

IT WAS NOT DESIGNED, TESTED OR RECOMMENDED FOR THIS 
USE.

•  DO NOT USE THIS PRODUCT IN HAZARDOUS LOCATIONS (E.G. 

EXPLOSIVE ATMOSPHERES). IT WAS NOT DESIGNED, TESTED OR 
RECOMMENDED FOR THIS USE.

•  ENSURE THE PRODUCT IS PROPERLY WIRED TO THE CORRECT 

POWER SUPLLY FOR THE APPLICATION. REFER TO THE 
SPECIFICATIONS AND WIRING DIAGRAMS IN THIS MANUAL.

MODELS COVERED IN THIS MANUAL

Catalog Number

Description

EGF1NCLA050

120V AC, N.C. SPST Relay, 50 mA Setpoint

EGF1NOLA050

120V AC, N.O. SPST Relay, 50 mA Setpoint

EGF1NCLA100

120V AC, N.C. SPST Relay, 100 mA Setpoint

EGF1NOLA100

120V AC, N.O. SPST Relay, 100 mA Setpoint

EGF1NCLAT3

120V AC, N.C. SPST Relay, 5/10/30 mA Setpoint, Tri-Set

EGF1NOLAT3

120V AC, N.O. SPST Relay, 5/10/30 mA Setpoint, Tri-Set

EGF2NCLA050

24V AC/DC, N.C. SPST Relay, 50 mA Setpoint

EGF2NOLA050

24V AC/DC, N.O. SPST Relay, 50 mA Setpoint

EGF2NCLA100

24V AC/DC, N.C. SPST Relay, 100 mA Setpoint

EGF2NOLA100

24V AC/DC, N.O. SPST Relay, 100 mA Setpoint

EGF2NCLAT3

24V AC/DC, N.C. SPST Relay, 5/10/30 mA Setpoint, Tri-Set

EGF2NOLAT3

24V AC/DC, N.O. SPST Relay, 50/10/30 mA Setpoint, Tri-Set

INTRODUCTION

The CurrentWatch™ EGF Series is a family of 
ground fault (earth leakage) sensors. Ground 
fault sensors help protect people, products, and 
processes from damage by ground fault 
conditions by monitoring all current-carrying 
conductors in grounded single- and three-
phase delta or wye systems. 

The EGF Series with mechanical outputs are 
available in solid-core housings with a choice of N.O. or N.C. SPST 
latching relays. All mechanical models can be ordered with a fi xed 
setpoint or with a “tri-set” option, which provides three factory-set, fi eld 
adjustable setpoints.

Note that this manual only covers EGF Series models listed in the 
above table. This installation manual does not cover EGF Series 
models with auto-reset.  

QUICK INSTALL GUIDE

The below steps can be followed to quickly install a CurrentWatch™ 
EGF Series switch.

1.  Run all current carrying conductors through sensor window, using 

an auxiliary current transformer if conductors do not fi t

2.  Mount the sensor to a surface if needed
3.  Connect output and power wiring

a.  Use up to 14 AWG copper wires
b.  Ensure power and load matches those shown on the sensor 

label

4.  Test the unit

a.  Pressing the “TEST” button will test the sensor’s internal 

circuits

b.  CAUTION: The output and any connected loads will switch 

during the test process

INSTALLATION AND MOUNTING 

Considerations for all EGF Series sensors…

•  Run wire to be monitored through the aperture (opening) in the 

switch body, making sure all wires are oriented so that current 
fl ows in the same direction (see “Principal of Operation” section 
on reverse side)

•  These sensors can be located in the same environment as motors, 

contactors, heaters, pull-boxes and other electrical enclosures

•  Mounting can be done in any position or hung directly on a wire 

with a wire tie

•  Be sure to leave at least one inch distance between sensor and 

other magnetic devices 

Considerations for wiring EGF Series sensors…

•  Use up to 10 AWG copper wire and tighten terminals to 4.5 inch-

pounds torque

•  Connect power wiring to terminals 1 and 2, making sure that the 

power supply matches the power rating on the sensor label

•  Connect output wiring to terminals 3 and 4

PRINCIPAL OF OPERATION

Under normal conditions, the current in one wire of a two wire load is 
equal in strength but opposite in sign to the current in other wire. The 
two wires create magnetic fi elds that cancel, a condition known as 
“Zero Sum Current.” If any current leaks to ground (Ground Fault), the 
two currents become unbalances and there is a net resulting magnetic 
fi eld. The EGF Series sensor detects this minute fi eld and change the 
output state. This concept extends to three phase systems such as 3-
wire Delta and to 4-wire Wye.

Single Phase

(Phase to Neutral or 
Phase to Phase)

Three-Phase Delta

(Includes Neutral if 
Load Uses Neutral)

Three-Phase Wye

(Include Neutral if 
Load Uses Neutral)

Three-Phase Load 

(Using Auxiliary CT)

P51923

 Rev 01

Effective: April 2007

Page 1

WARNING

Questions? Call our Sensor Application Engineers at (800) 426-9184.

490050021

Installation Instructions

CurrentWatch™ EGF Series Ground Fault Sensors