I.B. ATS-V003
Page 21
Effective 6/98
BE SURE THAT THE CORRECT VOLTAGE IS
SELECTED TO MATCH THE SYSTEM VOLTAGE. AN
IMPROPER SELECTION AND/OR CONNECTION
COULD RESULT IN EQUIPMENT DAMAGE.
Vertical Design Voltage Selection
The vertical design transfer switch is furnished with a
multi-tap Voltage Selection Panel to the right of the
power panel. Seven front accessible taps from 208 to
600 volts AC are provided (Figure 3-4). A small discon-
nect plug is provided to change from one voltage to
another.
Horizontal Design Voltage Selection
Horizontal design transfer switches are furnished with an
adjustable line voltage plug and receptacles below the
power panel. To change the line voltage, remove the
covers and insert the plug in the desired receptacle
(Figure 4-6).
!
CAUTION
Summary of Contents for Cutler-Hammer ATVSKDA30300XSU
Page 2: ......
Page 36: ...I B ATS V003 Page 30 Effective 6 98...
Page 37: ...I B ATS V003 Page 31 Effective 6 98...
Page 38: ...I B ATS V003 Page 32 Effective 6 98...
Page 39: ......