![background image](http://html1.mh-extra.com/html/eaton/currentwatch-edc-series/currentwatch-edc-series_instruction-leaflet_524451003.webp)
Troubleshooting
Problem
Solution for Current
Output Models
Sensor has no
output.
Monitored load is not DC or is not on. Check that the moni-
tored load is DC and that it is actually on.
Polarity is not properly matched. Check and correct wiring
polarity.
Output signal is
too low.
The jumper may be set in a range that is too high for current
being monitored. Move jumper to the correct range.
Power supply is inadequate. Check power supply. Make sure
it is of sufficient voltage with all loads at maximum. The cur-
rent draw of EDC Series sensors is 2.0 VA.
Output load is too high. Check output load, being sure it is no
more than 500 ohms.
Output signal is
always at maxi-
mum.
The jumper may be set in a range that is too low for current
being sensed. Change the jumper position.
Specifications
Specification
Value
Power Supply
24 VAC/DC (22-28 VAC/DC)
Power input and output signal are not isolated.
Caution:
Do not connect Grounded AC Supply to the
Output Negative (-), as sensor damage may occur.
Power Consumption
2 VA
Current Ranges
Jumper Selectable: 5, 10, or 20 A
Output Signal
4-20 mA
Response Time
160 ms (90% of Step Change)
Repeatability
1% FS
Frequency Range
DC
Accuracy
1% FS
Linearity
0.75%
Isolation Voltage
3 kV (Monitored Line to Output)
Sensing Aperture
0.75 in. (19 mm) dia.
Housing
UL94 V0 Flammability Rated
Environmental
Operating Temperature: -4 to +122°F (-20 to +50°C)
Humidity: 0-95% RH, Non-Condensing
Approvals
UL Listed, E117028
UL tested to Canadian safety standards
CE
RoHs Compliant
3
EATON
www.eaton.com
Instructions Publication
P51926
Effective July 2017
CurrentWatch™ EDC Series Current Sensors,
DC Current Sensor, Solid Core Housing with
Analog Output