LED Indication / Output Status

Monitored Amps

Output

Smart-LED  

(If Present)

N.O.

N.C.

None or Minimum

Open

Closed

Off

Below Trip Level

Open

Closed

Slow (2 sec.)

Above Trip Level

Closed

Open

Fast (0.5 sec.)

Wiring Diagram

Connect control or monitoring wires to the sensor. Use up to 14 

AWG copper wire and tighten terminals to 7 in.-lbs / 0.79 N·m maxi-

mum torque. Be sure the output load does not  exceed the solid 

state output rating. 

Ranges and Maximum Amps

Housing

Range

Maximum Amps

Continuous 6 sec.

1 sec.

Solid Core

1.5-175 A

150 A

400 A

1,000 A

Split Core

2-200 A

150 A

400 A

1,000 A

CAUTION

 

INCANDESCENT  LAMPS CAN 
HAVE “COLD  FILAMENT INRUSH” 
CURRENT OF  UP TO TEN TIMES 
THEIR RATED  AMPERAGE. USE 
CAUTION  WHEN SWITCHING 
LAMPS

.

AC or DC

Power

AC or DC

Load

Output Signal

To Monitored Load

Use caution when

switching lamps

Hysteresis

Setting Hysteresis

Low

<

 

0.01 A

Mid

<

 

0.1 A

High

<

 

0.5 A

Switching Delay

Delay Type

Low Range

Mid Range

High Range

On Delay

0.23 sec. max.

0.05 sec. max.

0.03 sec. max.

Off Delay

0.02 sec. max.

0.02 sec. max.

0.01 sec. max.

Troubleshooting

Problem

Solution

Switch is  

always 

tripped.

The setpoint may be too low. Turn pot clock-wise to increase set-

point.
Switch may have been overloaded and contacts are burned out. 

Check the output load, remembering to include inrush on inductive 

loads (coils, motors).

Switch will 

not trip.

The setpoint may be too high. Turn pot counter-clockwise to 

decrease setpoint.
For split core models, the core contact area may be dirty. Open the 

sensor and clean the contact area.
The monitored current may be below the minimum required. Loop the 

monitored wire several times through the aperture until the “sensed” 

current rises above the minimum. The sensed amps equals “actual 

amps” multiplied by the “number of loops.” Count loops on the 

inside of the aperture.
Switch may have been overloaded and contacts are burned out. 

Check the output load, remembering to include inrush on inductive 

loads (coils, motors).

Specifications

Specification

Value

Power Supply

Self Powered – No Power Supply Needed

Output

Magnetically Isolated Solid State Switch

Output Rating

AC-Only Models: N.O./N.C. 1 A @ 240 VAC 

AC/DC Models:

   N.O. 0.15 A @ 240 VAC/DC 

   N.C. 0.20 A @ 135 VAC/DC

Off-State Leakage

ECSTD402SC and ECSTD405SP Models: 2.5 mA 

All Other Models: Negligible

Response Time

Adjustable, 0.12 to 15 seconds

Setpoint Range

Solid Core Models: 1.5-12, 12-55 and 50-175A 

Split Core Models: 2-12, 12-55 and 50-200A

Setpoint Adjustment

Solid Core Models: 15-Turn Potentiometer 

Split Core Models: 4-Turn Potentiometer

Hysteresis

Constant 5% of Setpoint

Overload

See “Ranges and Maximum Amps” in Table

Isolation Voltage

UL Listed to 1,270 VAC, Tested to 5,000 VAC

Frequency Range

50-100 Hz

Sensing Aperture

Solid Core Models: 0.75 in. (19 mm) dia. 

Split Core Models: 0.85 in. (21.7 mm) sq.

Housing

UL94 V0 Flammability Rated

Environmental

Operating Temperature: -58 to +149°F (-50 to +65°C)

Humidity: 0-95% RH, Non-Condensing

Approvals

UL Listed, E117028

UL tested to Canadian safety standards

CE

RoHs Compliant

(ECSTD401SC and ECSTD402SC not UL or cUL listed)

3

EATON 

www.eaton.com

 

Instructions Publication 

P51921

Effective July 2017

CurrentWatch™ ECSTD Series 