background image

IN ORDER TO AVOID ELECTRIC SHOCK OR OTHER POSSIBLE INJURY:

•  DO NOT USE THIS PRODUCT FOR HUMAN SAFETY APPLICATIONS. 

IT WAS NOT DESIGNED, TESTED OR RECOMMENDED FOR THIS 
USE.

•  DO NOT USE THIS PRODUCT IN HAZARDOUS LOCATIONS (E.G. 

EXPLOSIVE ATMOSPHERES). IT WAS NOT DESIGNED, TESTED OR 
RECOMMENDED FOR THIS USE.

•  ENSURE THE PRODUCT IS PROPERLY WIRED FOR THE 

APPLICATION. REFER TO THE SPECIFICATIONS AND WIRING 
DIAGRAMS IN THIS MANUAL.

MODELS COVERED IN THIS MANUAL

Catalog Number

Description

ECSNOASC

Self-Powered, Solid Core, N.O., Adjustable Setpoint (1-150A), LED

ECSNOFSC

Self-Powered, Solid Core, N.O., Fixed Setpoint (1.0A), No LED

ECSNCASC

Self-Powered, Solid Core, N.C., Adjustable Setpoint (1-150A), LED

ECSNCFSC

Self-Powered, Solid Core, N.C., Fixed Setpoint (1.0A), No LED

ECSNOASP

Self-Powered, Split Core, N.O., Adjustable Setpoint (1.75-150A), LED

ECSNOFSP

Self-Powered, Split Core, N.O., Fixed Setpoint (1.5A), No LED

ECSNCASP

Self-Powered, Split Core, N.C., Adjustable Setpoint (1.75-150A), LED

ECSNCFSP

Self-Powered, Split Core, N.C., Fixed Setpoint (1.5A), No LED

INTRODUCTION

The Cutler-Hammer 
CurrentWatch™ ECS Series are 
a family of self-powered, solid-
state current-operated switches 
which trigger when the current 
level sensed through the 
aperture exceeds the adjusted 
setpoint. The solid-state output contacts can 
switch AC or DC, making the ECS Series well 
suited for applications in automation systems.

Eaton’s current sensor family encompasses a broad range of products 
for cost-effective monitoring, status, and predictive maintenance. 
Downtime and costly repairs can be avoided by utilizing Eaton’s 
products and technologies in your control systems.

Installation Instructions

CurrentWatch™ ECS Series Current Switch

AC Current Switch, Fixed or Adjustable Setpoint

INSTALLATION

Considerations for all ECS Series models…

•  Run wire to be monitored through the aperture (opening) in the 

switch body

•  These switches can be located in the same environment as 

motors, contactors, heaters, pull-boxes and other electrical 
enclosures

•  Mounting can be done in any position or hung directly on wires 

with a wire tie 

Considerations for split core versions (-SP suffi x)…

•  To open the switch, press the tab inward (toward the body of the 

switch) as shown below

•  After placing the wire in the aperture, press the hinged portion 

fi rmly downward until a click is heard and the tab pops out fully

•  Keep the contact areas of split-core switches clean at all times

QUICK INSTALL GUIDE

The below steps can be followed to quickly install a CurrentWatch™ 
ECS Series switch.

1.  Run the wire to be monitored through the aperture
2. Mount the switch
3. Connect output wiring

a.  Use up to 14 AWG copper wires
b.  Use caution not to exceed solid state output rating (see 

specifi cation table on following page)

3. Adjust the setpoint

a.  Use the potentiometer to adjust the setpoint

LED

 

/

 

OUTPUT STATUS TABLE

Monitored Amps

Output

Smart-LED 
(If Present)

N.C.

N.O.

None or Minimum

Closed

Open

Off

Below Trip Level

Closed

Open

Slow (2 sec.)

Above Trip Level

Open

Closed

Fast (0.5 sec.)

P51916

 Rev 02

Effective: January 2008

Page 1

WARNING

Questions? Call our Sensor Application Engineers at (800) 426-9184.

To open:

Press tab inward
towards hinge

Important:

Keep contact areas clean

392500221

Reviews: