14. TECHNICAL DATA

Hazardous Location Technical Data for Breakers

Explosion Category:

     For USL

     For CNL

AEx de IIB/IIC

Ex de IIB/IIC

Certifications and Compliances:

For USL

Class I, Division 2, Groups A, B, C, D

Class I, Zone 1

For CNL

Class I, Division 2, Groups A, B, C, D

Zone 1

Ambient Temperature  Range

IIB: -45°C to +55°C (GHG62-1/2...R...)

IIB and IIC: -20°C to +40°C (GHG627...R...)

IIC: -20°C to +55°C (GHG62-1/2/3/4...R...)

Permissible Service Temperature Range*

IIB: -45°C to +110°C (GHG62-1/2...R...)

IIB and IIC: -20°C to +110°C (GHG627...R...)

IIC: -20°C to +110°C (GHG62-1/2/3/4...R...)

*Other temperatures possible with special versions.

Certifications and Ratings

Certifications and Compliances:

cULus Listed 

Class I, Division 2, Groups A, B, C, D

Class II, Division 2, Groups F and G

Zone 2 Ex ec IIC Gc T4

Zone 22 

UL67 

CSA C22.2 No. 29

UL60079-7

CSA-C22.2 No.60079-15:2012

IP66

Temperature class: T4

Ambient Temperature Range - Standard:-20°C to +55°C

Ambient Temperature Range - HT1 & HT2 Options :-40°C to +55°C

Rated Voltage

Up to 480/277 VAC, 60 Hz

Rated Short Circuit Current

10 kA

Rated Current

Max. 225A

up to 55°C 

Environmental Rating

3R, 4, 4X with stainless steel enclosure

Temperature Class

T4

Ambient Temperature

-20°C to +55°C (default)

-40°C to +55°C (with HT1 and HT2 suffix)

Entries

Acc. to customer’s specification and as certified (consult factory)

Terminal Cross-section – Incoming

MLO: 6 AWG  - 250MCM (10mm2 - 120mm2)

MCB: 11 AWG - 350 MCM (4mm2 - 185mm2)

Incoming Wires

75°C

Outgoing Wires

75°C

Enclosure Material

Stainless steel

Mechanical Data – Circuit Breakers

Terminal Specifications

Branch and on-chassis main 

(10A - 40A)

Off-chassis main (>50A)

Terminal Size

14 - 8 AWG

1.5mm

2

 - 16mm

2

11 AWG - 350 MCM

4mm

2

 - 185mm

2

Aux. Terminals

AWG 14

AWG 11 - 20

Quantity Terminals for the Module Size:

     Main Terminals

     Aux. Terminals

1P       2P       EPD/GFI       3P       Main Breaker
1         2         2                  3         3

2         3         3                  4         5

Torques:

     Main Contacts

     Aux. Contacts

     Mounting Screws

31 in.-lb. (3.5 N-m)

22 in.-lb. (2.5 N-m)

18 in.-lb. (2 N-m)

89 in.-lb. (10 N-m)

22 in.-lb. (2.5 N-m)

18 in.-lb. (2 N-m)

Summary of Contents for Crouse-Hinds SynergEX EZFlex Series

Page 1: ...NFORMITY WITH STANDARDS 3 TRANSPORT STORAGE To store SynergEX Panelboards shall be placed on a clean dry and flat surface whereby the position shall be maintained SynergEX Panelboards shall be protect...

Page 2: ...nent location proceed to punching field entries in panelboard enclosure where required and continue to Step 6 NOTE If gland plates were supplied proceed to Step 4 4 Remove gland plates and drill desir...

Page 3: ...f maximum load rating for continuous use 10 LOCKOUT The lockout on the MCB should be used whenever the operator is in the OFF position Ensure proper operation of lockout mechanism whenever the dead fr...

Page 4: ...1 1 FIRST MADE FOR SSP ASSEMBLY PANELBOARD APPROVED BY DRAWN BY mm in 13 000 1 5 JAF THIS IS PROPERTY OF EATON AND CONTAINS CONFIDENTIAL AND TRADE SECRET INFORMATION POSSESSION DOES NOT CONVEY ANY RI...

Page 5: ...lass T4 Ambient Temperature Range Standard 20 C to 55 C Ambient Temperature Range HT1 HT2 Options 40 C to 55 C Rated Voltage Up to 480 277 VAC 60 Hz Rated Short Circuit Current 10 kA Rated Current Max...

Page 6: ...ing Location Torque in lb Torque N m Busbar Mounting Screws 18 2 Heater Mounting Screws Lockout Device Nuts lockout assembly to deadfront Window Nuts 22 2 5 Deadfront Bracket Mounting Nuts bracket to...

Page 7: ...6 54 166mm 0 22 5 5mm 2 83 72mm 2 13 54mm X 2 40 61mm 5 20 132mm 4 49 114mm 4 02 102mm 0 22 5 5mm 6 97 177mm X 6 54 166mm X 3 82 97mm 4 25 108mm 5 20 132mm 4 49 114mm 4 02 102mm 2 13 54mm 1 pole 277 V...

Page 8: ...anch and On Chassis Main available as optional The technical data relates to standard built in apparatus If other built in apparatus is used the technical data sheets or the data on the type label sha...

Reviews: