SynergEX Panelboards have been designed, manufactured and tested according to the 

following standards:

• 

cULus Listed

• 

Class I, Division 2, Groups A, B, C, D

• 

Class II, Division 2, Groups F and G

• 

Zone 2 Ex ec IIC Gc T4

• 

Zone 22 

• 

UL67 

• 

CSA C22.2 No. 29

• 

UL60079-7

• 

CSA-C22.2 No.60079-15:2012

• 

IP66

 SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

IF 1911

SynergEX EZFlex Panelboards

for Hazardous Locations

Installation & Maintenance Information

IF 1911 • 09/20                                                        Copyright

©

 2020, Eaton’s Crouse-Hinds Division 

                                                      Page 1

Figure 1 – Dimensions (inches)

WARNING

To avoid fire, shock and/or explosion,

 

This product must be installed, inspected and maintained by qualified personnel in 

accordance with all applicable codes and these instructions.
All electrical power sources must be OFF and locked out, and the area must be 

free of flammable or explosive gases, vapors or dusts before performing any 

maintenance.
All wiring must be suitable for the area, and must comply with the nameplate 

ratings and these instructions.
Do not install where the marked operating temperature exceeds the ignition 

temperature of the hazardous atmosphere.
Do not operate in ambient temperatures outside of the nameplate markings. See 

temperature limits in Technical Data section. For product with HT1 or HT2 options, 

do not turn product ON when ambient temperature is less than -20°C. Ensure the 

heating system is operational and stabilized prior to turning the circuit breaker ON.
Do not use this equipment for other than intended use.
Keep tightly closed when in operation.
The maximum continuous load shall not exceed 80% of the rating of the main 

circuit breaker.
Only certified cable or conduit entries and stopping plugs may be used.

!

1. APPLICATION

SynergEX Panelboards provide short circuit protection for feeder circuit to control 

lighting, motor and similar circuits.
SynergEX Panelboard is designed for use in Class I, Zone 2, Division 2, Groups A, B,  

C, D (classified) areas as defined by the National Electrical Code® (NEC) and Canadian 

Electrical Code (CEC), as well as in damp, wet locations – indoors and outdoors.

2. CONFORMITY WITH STANDARDS

3. TRANSPORT/STORAGE

To store, SynergEX Panelboards shall be placed on a clean, dry and  flat  surface, 

whereby the position shall be maintained. SynergEX Panelboards shall be protected 

against adverse weather conditions. Transport storage temperature: -20°C to +55°C.

Panelboard should be installed, inspected, maintained and operated by qualified and 

competent personnel. Read entire instructions before starting installation and operation 

of this product. Contact your Eaton’s Crouse-Hinds Division sales representative, 

customer service or Crouse-Hinds distributor if you have any questions.

CAUTION

To avoid nuisance tripping avoid direct exposure to sunlight.

!

Encl. 

size

A

B

C

D

E

F

G

H

I

Weight

A

30.00

(762)

24.00

(610)

10.00

(254)

31.56

(801)

22.38

(568)

28.50

(723)

24.43

(646)

23.00

(584)

17.63

(448)

140 lbs.

64 kg.

B

34.00

(863)

24.00

(610)

10.00

(254)

35.56

(903)

22.38

(568)

32.50

(825)

24.43

(646)

27.00

(685)

17.63

(448)

158 lbs.

72 kg.

C

39.00

(990)

24.00

(610)

10.00

(254)

40.56

(1030)

22.38

(568)

37.50

(952)

24.43

(646)

32.00

(812)

17.63

(448)

182 lbs.

83 kg.

D

43.00

(1092)

24.00

(610)

10.00

(254)

44.56

(1131)

22.38

(568)

41.50

(1054)

24.43

(646)

36.00

(914)

17.63

(448)

200 lbs.

91 kg.

E

47.00

(1193)

24.00

(610)

10.00

(254)

48.56

(1233)

22.38

(568)

45.50

(1155)

24.43

(646)

40.00

(1016)

17.63

(448)

219 lbs.

99 kg.

F

52.00

(1320)

24.00

(610)

10.00

(254)

53.56

(1360)

22.38

(568)

50.50

(1282)

24.43

(646)

45.00

(1143)

17.63

(448)

242 lbs.

110 kg.

G

56.00

(1422)

24.00

(610)

10.00

(254)

57.56

(1462)

22.38

(568)

54.50

(1384)

24.43

(646)

49.00

(1244)

17.63

(448)

261 lbs.

118 kg.

H

69.00

(1752)

24.00

(610)

10.00

(254)

70.56

(1792)

22.38

(568)

67.50

(1714)

24.43

(646)

62.00

(1574)

17.59

(447)

321 lbs.

146 kg.

1. 

Select a mounting location that will provide suitable strength and rigidity for 

supporting the SynergEX Panelboards and all components. Install the top two 

(2) mounting screws; then install the bottom two (2) mounting screws. Securely 

torque all screws around enclosure before removing support.

2. 

The enclosure shall rest evenly only on the fastening points provided for this 

purpose, and they shall be fixed in such a way that they cannot twist or turn.
The screws used shall match the fixing holes (see Figure 1) and must not 

damage the openings (e.g. use of washers).

4. GENERAL INSTALLATION

CAUTION

Excessive tightening can result in damage to SynergEX panelboards.

!

Summary of Contents for Crouse-Hinds SynergEX EZFlex Series

Page 1: ...NFORMITY WITH STANDARDS 3 TRANSPORT STORAGE To store SynergEX Panelboards shall be placed on a clean dry and flat surface whereby the position shall be maintained SynergEX Panelboards shall be protect...

Page 2: ...nent location proceed to punching field entries in panelboard enclosure where required and continue to Step 6 NOTE If gland plates were supplied proceed to Step 4 4 Remove gland plates and drill desir...

Page 3: ...f maximum load rating for continuous use 10 LOCKOUT The lockout on the MCB should be used whenever the operator is in the OFF position Ensure proper operation of lockout mechanism whenever the dead fr...

Page 4: ...1 1 FIRST MADE FOR SSP ASSEMBLY PANELBOARD APPROVED BY DRAWN BY mm in 13 000 1 5 JAF THIS IS PROPERTY OF EATON AND CONTAINS CONFIDENTIAL AND TRADE SECRET INFORMATION POSSESSION DOES NOT CONVEY ANY RI...

Page 5: ...lass T4 Ambient Temperature Range Standard 20 C to 55 C Ambient Temperature Range HT1 HT2 Options 40 C to 55 C Rated Voltage Up to 480 277 VAC 60 Hz Rated Short Circuit Current 10 kA Rated Current Max...

Page 6: ...ing Location Torque in lb Torque N m Busbar Mounting Screws 18 2 Heater Mounting Screws Lockout Device Nuts lockout assembly to deadfront Window Nuts 22 2 5 Deadfront Bracket Mounting Nuts bracket to...

Page 7: ...6 54 166mm 0 22 5 5mm 2 83 72mm 2 13 54mm X 2 40 61mm 5 20 132mm 4 49 114mm 4 02 102mm 0 22 5 5mm 6 97 177mm X 6 54 166mm X 3 82 97mm 4 25 108mm 5 20 132mm 4 49 114mm 4 02 102mm 2 13 54mm 1 pole 277 V...

Page 8: ...anch and On Chassis Main available as optional The technical data relates to standard built in apparatus If other built in apparatus is used the technical data sheets or the data on the type label sha...