41
SPEAR™ Single-Phase Recloser System
INSTALLATION AND OPERATION INSTRUCTIONS
MN280048EN June 2016
12. Perform a battery test on the new battery (assuming it
has been adequately charged) to confirm the state of
the new battery and wire assembly connections. Refer
to the
Battery test and charging procedures
section.
Return the control to service
After the required work is completed, proceed as follows:
1. Remove AC power from the control.
2. Disconnect the control battery.
3. Disconnect the control from the test set.
Follow this procedure to return the control to service:
1. Appropriate personnel must verify that all control
settings are correct.
2. Reconnect the ground cable to the control.
3. Control cable properly connected, fully tightened to
ensure gasket seal, and supported on both ends.
4. Plug in the control battery.
otee:
N
The SPEAR single-phase recloser control will not
automatically power up until AC power is applied.
5. Apply AC power to the control.
6. Verify the control clock is set to the current time after
AC power has been reapplied.
otee:
N
The control clock may require resetting if the
operating power has been disconnected for more
than thirty days. Refer to
Service Information
MN280012EN SPEAR Single-Phase Recloser Control
Programming Guide
for information on setting the
control clock.
Figure 44 .
Wing
nut
Wing
nut
Wing
nut
Reinstall wing nuts and battery bracket
Additional information
CAUTION
This equipment requires routine inspection and
maintenance to ensure proper operation . If it is not
maintained, it can fail to operate properly . Improper
operation can cause equipment damage and possible
personal injury .
G105 .1
Replacement kits
Replacement parts kits for the SPEAR single-phase
recloser control are available through the factory Service
Department. Only factory-authorized parts are to be used.
To order replacement parts, refer to
Parts Guide S260-01
through S280-01
for catalog numbers. Contact your Eaton
representative for additional information and ordering
procedures.
Factory-authorized service centers
Factory-authorized service centers are located throughout
the continental United States to provide maintenance, repair
and testing services for Eaton’s Distribution Switchgear
products. Refer to
Service Centers Brochure B100-04009
for
the Authorized Service Center closest to your location. For
further information, contact your Eaton representative.
Factory maintenance classes
The factory service department offers a basic testing
and troubleshooting course for the SPEAR single-phase
recloser system. This course, taught by experienced
service technicians, is held at the factory’s in-house training
facility. For additional information, contact your Eaton
representative.
Type MET recloser control tester
A 30-minute video program KSPV7 Kyle Type MET Electronic
Recloser Control Tester Operation and Testing Procedures
is available as a supplemental training aid for service
personnel.