 warning

(1) Only qualified electrical persOnnel shOuld 

be permitted tO wOrk On the equipment.  

(2) always de-energize primary and  

secOndary circuits if a circuit breaker  

cannOt be remOved tO a safe wOrk lOcatiOn. 

(3) drawOut circuit breakers shOuld be levered 

(racked) Out tO the discOnnect  

pOsitiOn. 

(4) all circuit breakers shOuld be switched  

tO the Off pOsitiOn and mechanism springs 

discharged. 

failure tO fOllOw these steps fOr all  

prOcedures described in this instructiOn  

leaflet cOuld result in death, bOdily injury,  

Or prOperty damage.

 warning

the instructiOns cOntained in this awa and On 

prOduct labels have tO be fOllOwed. Observe 

the five safety rules: 

–   discOnnecting 

–   ensure that devices cannOt be  

  accidentally restarted 

–   verify isOlatiOn frOm the supply 

–   earthing and shOrt-circuiting 

–   cOvering Or prOviding barriers tO  

  adjacent live parts 

discOnnect the equipment frOm the supply. 

use Only authOrized spare parts in the repair 

Of the equipment. the specified maintenance 

intervals as well as the instructiOns fOr 

repair and exchange must be strictly adhered 

tO prevent injury tO persOnnel and damage tO 

the switchbOard.

Section 1: General information

This key interlock provides the following  

safety features:

• 

With no key, the breaker is open and  

cannot close

• 

With the key ON (in cylinder) and rotated,  

the breaker is fully functional

• 

The key cannot be removed when the  

breaker is ON (closed). The key cannot turn  

the breaker OFF

Note:

N

To remove the key, press the breaker OFF button, 

and rotate the key 90 degrees counterclockwise.

Rtquirtd oNNls

• 

M10 socket with 1/4-inch drive 

• 

1-7/16-inch (36 mm) hole saw/drill

• 

#1 Phillips head screwdriver

• 

Flat blade screwdriver

• 

Needle-nose pliers

Kio paros idtnoificaoiNn

Refer to 

Figurt 1

 for visual identification of the 

parts listed below:
(A) Interlock arm assembly
(B) Castell lock CL1019 with key CL1062— 

specify unique lock lettering code when ordering 

(Castell keylock not supplied)
(C) Castell keylock mounting plate
(D) Interlock adapter
(E) Hold-down bracket
(F) Torsion spring
(G) Spring pin
(H) Hex standoff
(I) Extension spring
(J) Adapter screw
(K) Standoff screw (1/8-inch shoulder)
(L) Interlock cable
(M) Retaining clip (M5 x 0.7)
(N) Interlock lever
(O) Lock mounting plate screw (three)
(P) Interlock lever screw (M3.5 x 10 tapping)

Summary of Contents for Castell IZM-KLP-SO-CASTELL

Page 1: ...ervals as well as the instructions for repair and exchange must be strictly adhered to prevent injury to personnel and damage to the switchboard Section 1 General information This key interlock provides the following safety features With no key the breaker is open and cannot close With the key ON in cylinder and rotated the breaker is fully functional The key cannot be removed when the breaker is ...

Page 2: ...nstalled remove and save these items for later re installation Remove existing counter lock mounting plate and discard it Figure 3 Step 3 Keylock Hole Location Mounting Bolts Operations Counter Mounting Plate Step 4 Snap the interlock arm assembly A into place on the shaft as shown Figure 4 Step 4 Step 5 Remove existing screws from the back of the lock cylinder B and use one screw to mount the loc...

Page 3: ...e the spring winding direction as shown in the side view Figure 8 Step 8 Cable L Standoff Screw K Hex Standoff H Interlock Adapter D Adapter Screw J Note Orientation Hold Down Bracket E Side View Spring Pin G Torsion Spring F Step 9 Mount the assembly from Step 8 to the breaker as shown using three lock plate mounting screws O Connect the extension spring I between the interlock arm assembly and t...

Page 4: ...0 Step 11 Rotate the key counterclockwise to lock out interlock as shown If an operations counter was previously removed in Step 3 re install it to the back of the new lock mounting plate using two M3 5 x 8 mm self tapping screws Refer to Operations Counter IL for installation instructions Figure 11 Step 11 Step 12 Re install the front cover removed in Step 1 Key removal is required to install the...

Page 5: ...valle sowie die Anweisungen für Reparatur und Austausch sind unbedingt einzuhalten um Schäden an Personen und Anlagen zu vermeiden Abschnitt 1 Allgemeine Informationen Das Schloss bietet die folgenden Sicherheitsfunktionen Wenn der Schlüssel nicht eingesteckt ist bleibt der Schalter ausgeschaltet und kann nicht eingeschaltet werden Mit eingestecktem Schlüssel ist der Schalter voll funktionsfähig D...

Page 6: ...bdeckung Nutzen Sie die Einkerbung auf der Innenseite der Frontabdeckung als Orientierung Benutzen Sie eine Lochsäge Abbildung 2 Schritte 1 und 2 Einbauposition der Abschließvorrichtung Schraube Schritt 3 Sollte ein Schaltspielzähler eingebaut sein dann entfernen Sie diesen mitsamt Feder die Teile werden nach Abschluss der Installation wieder eingebaut Entfernen Sie die Montageplatte des Schaltspi...

Page 7: ...mmen Achten Sie dabei auf die Ausrichtung des Schlüssels und des Abstandsbolzens Abbildung 7 Schritt 7 Schraube mit der Hand nur leicht eindrehen Castell Schloß B nicht im Lieferumfang Castell Schloß Montageplatte C Stechplatz Schließzylinder Ausrichtung Schlüssel sollte für diesen Schritt gesteckt sein Verbindungskabel L Schraube K Schraube H Adapterplatte D Befestigungsschrauben Adapterplatte J ...

Page 8: ...rauben Sie das Verbindungskabel mit der Gewindeformenden Schraube P an den Auslösehebelarm siehe Abbildung 10 Abbildung 10 Schritt 10 Sicherungsring M Verriegelungshebel N Befestigungsschrauben Adapterplatte P Schritt 11 Drehen Sie den Schlüssel wieder entgegen dem Uhrzeigersinn Sollte der Schalter mit einem Schaltspielzähler ausgestattet sein welcher zuvor entfernt wurde so schrauben Sie diesen m...

Reviews: