Fault 007
, Fan Lock
Start
Fans is connected rightly
Connect them
(1-1.5 front panel FAN
2-3K front and rear panel FAN)
N
Restart UPS and no
alarm?
End
N
Fans on rear and front panel
are rotating?
Y
Y
Replace Fans
N
Restart UPS and no
alarm?
N
End
Y
Replace CNTL
Y
Restart UPS and no alarm?
N
Y
Replace UPS
End
UPS
CNTL
End
Repair detection
circuit
Restart UPS and no alarm?
N
End
PSDR
Replace PSDR PCBA
Y
Restart UPS and no alarm?
End
N
Y