Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
141
Table 26. Environmental and Safety (Continued)
BladeUPS 12 Model
BladeUPS 12i
Model
BladeUPS 8 Model
BladeUPS 5.0
Model
Leakage Current
<3.5 mA
Communication
DB-9: 1200–19200 baud
Table 27. Battery
UPS Internal
Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
Configuration
(40) 12V, 5 Ah
(20) 12V, 5Ah
(5.0 kW only)
(20) 12V, 9 Ah
(40) 12V, 9 Ah
(60) 12V, 9 Ah
(80) 12V, 9 Ah
Type
Sealed, maintenance-free, valve-regulated, lead-acid
Monitoring
Advanced monitoring for earlier failure detection and warning
Charging (in
minutes)
8–10 times the discharge time
NOTE
Charging times are approximate and are to 80% usable capacity at nominal line voltage after full load discharge.
Table 28. Standalone UPS Battery Runtimes at Full/Half Load (in Minutes)
Model
kW
UPS Internal
Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
BladeUPS 12
12/6
4.7/13.6
9.5/27
17/42
27/60
34/76
BladeUPS 12i
12/6
4.7/13.6
9.5/27
17/42
27/60
34/76
BladeUPS 8
8/4
8.7/23
17.7/41.5
27.9/65.5
43.0/94.1
54.7/120
BladeUPS 5.0
Single battery
string
5.0/2.5
6.2/16.1
21.7/45.8
37.2/80.1
59.2/128
79.0/175
BladeUPS 5.0
Two battery
strings
5.0/2.5
18.5/36.2
33/68.1
51.7/109.4
73/157.4
94.4/203.5
NOTE
Battery times are approximate and vary depending on the load configuration and battery charge.
Table 29. Parallel UPS System Battery Runtimes at Full/Half Load (in Minutes at Capacity)
Number of
UPSs
kW
UPS Internal
Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
2
24/12
4.7/13.6
9.5/27
17/42
27/60
34/76
3
36/18
4.7/13.6
9.5/27
17/42
27/60
34/76
4
48/24
4.7/13.6
9.5/27
17/42
27/60
34/76
Summary of Contents for BladeUPS none
Page 8: ...viii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Table of Contents ...
Page 12: ...xii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Figures ...
Page 14: ...xiv Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Tables ...
Page 20: ...6 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Introduction ...
Page 134: ...120 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Metering ...
Page 160: ...16420164914 164201649 14 ...